ELECTRICAL
Ground ambient temperature: 20ºC
Current Carrying Capacity
NOMINAL CROSS SECTIONAL AREA mm² |
REFERENCE METHOD C (CLIPPED DIRECT) Amps |
REFERENCE METHOD E (IN FREE AIR OR ON A PERFORATED CABLE TRAY, HORIZONTAL OR VERTICAL) Amps |
REFERENCE METHOD D (DIRECT IN GROUND OR IN DUCTING IN GROUND, IN OR AROUND BUILDINGS) Amps ` |
NOMINAL CROSS SECTIONAL AREA mm² |
REFERENCE METHOD C (CLIPPED DIRECT) Amps |
REFERENCE METHOD E (IN FREE AIR OR ON A PERFORATED CABLE TRAY, HORIZONTAL OR VERTICAL) Amps |
REFERENCE METHOD D (DIRECT IN GROUND OR IN DUCTING IN GROUND, IN OR AROUND BUILDINGS) Amps ` |
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
1 Two Core Cable Single-Phase AC or DC |
1 Three or 1 Four Core Cable Three-Phase AC |
| 1/5 |
27 |
23 |
29 |
25 |
25 |
21 |
| 2/5 |
36 |
31 |
39 |
33 |
33 |
28 |
| 4 |
49 |
42 |
52 |
44 |
43 |
36 |
| 6 |
62 |
53 |
66 |
56 |
53 |
44 |
| 10 |
85 |
73 |
90 |
78 |
71 |
58 |
| 16 |
110 |
94 |
115 |
99 |
91 |
75 |
| 25 |
146 |
124 |
152 |
131 |
116 |
96 |
| 35 |
180 |
154 |
188 |
162 |
139 |
115 |
| 50 |
219 |
187 |
228 |
197 |
164 |
135 |
| 70 |
279 |
238 |
291 |
251 |
203 |
167 |
| 95 |
338 |
289 |
354 |
304 |
239 |
197 |
| 120 |
392 |
335 |
410 |
353 |
271 |
223 |
| 150 |
451 |
386 |
472 |
406 |
306 |
251 |
| 185 |
515 |
441 |
539 |
463 |
343 |
281 |
| 240 |
607 |
520 |
636 |
546 |
395 |
324 |
| 300 |
698 |
599 |
732 |
628 |
446 |
365 |
| 400 |
787 |
673 |
847 |
728 |
- |
- |
Air ambient temperature: 30ºC
Ground ambient temperature: 20ºC
Conductor operating temperature: 90ºC
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² |
WO CORE CABLE SINGLE-PHASE AC mV/A/m |
THREE OR FOUR CORE CABLE THREE-PHASE AC |
NOMINAL CROSS SECTIONAL AREA mm² |
WO CORE CABLE SINGLE-PHASE AC mV/A/m |
THREE OR FOUR CORE CABLE THREE-PHASE AC |
| 1/5 |
31 |
27 |
| 2/5 |
19 |
16 |
| 4 |
12 |
10 |
| 6 |
7/9 |
6/8 |
| 10 |
4/7 |
4 |
| 16 |
2/9 |
2/5 |
| |
r |
x |
z |
r |
x |
z |
| 25 |
1/85 |
0/16 |
1/9 |
1/6 |
0/14 |
1/65 |
| 35 |
1/35 |
0/155 |
1/35 |
1/15 |
0/135 |
1/15 |
| 50 |
0/99 |
0/155 |
1 |
0/86 |
0/135 |
0/87 |
| 70 |
0/67 |
0/15 |
0/69 |
0/59 |
0/13 |
0/6 |
| 95 |
0/5 |
0/15 |
0/52 |
0/43 |
0/13 |
0/45 |
| 120 |
0/4 |
0/145 |
0/42 |
0/34 |
0/13 |
0/37 |
| 150 |
0/32 |
0/145 |
0/35 |
0/28 |
0/125 |
0/3 |
| 185 |
0/26 |
0/145 |
0/29 |
0/22 |
0/125 |
0/26 |
| 240 |
0/2 |
0/14 |
0/24 |
0/175 |
0/125 |
0/21 |
| 300 |
0/16 |
0/14 |
0/21 |
0/14 |
0/12 |
0/185 |
| 400 |
0/13 |
0/14 |
0/19 |
0/115 |
0/12 |
0/165 |
Conductor operating temperature: 90ºC
r = Resistive Component
x = Reactive Component
z = Impedance Value
For cables having conductors of 16mm2 or less cross sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm2, cross sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x.