APPLICATION

STANDARDS

VDE 0250 Part 812, VDE 0295, EN 60228 Flame Retardant according to IEC/EN 60332-1-2 Halogen Free according to IEC/EN 60754-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 3.6/6kV 6/10kV

Test Voltage 3.6/6kV: 11kV 6/10kV: 17kV

Maximum Short Circuit Temperature +250°C

Ambient Temperature : Fixed: -50°C to +80°C Flexed: -25°C to +80°C

Minimum Bending Radius : Fixed: 6 x overall diameter Flexed: 10 x overall diameter

Maximum Torsional Stress ±25°/m

CONSTRUCTION

Phase Conductor : Class 5 tinned copper conductor
Insulation : Rubber compound
Semi-Conductive Layers Semi-conductive tape over the conductor and inner and outer
semi-conductive rubber layer on the insulation
Protective Earth Conduc Individual copper screen
Control Conductor Class 5 tinned copper
Central Filler Rubber compound on a textile polyester support
Inner Sheath Halogen-free compound
Monitoring Conductor Copper wire screen over the first inner sheath
Outer Sheath Halogen-free PUR (Polyurethane)
Sheath Colour : Black

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS

VOLTAGE
kV
NO. OF CORES (PHASE + EARTH
+ CONTROL+ÜL)
NOMINAL CROSS  SECTIONAL AREA
mm2
CONDUCTOR DIAMETER
mm
MINIMUM OVERALL DIAMETER
mm
MAXIMUM OVERALL DIAMETER
mm
MAXIMUM TENSILE LOAD
N
NOMINAL WEIGHT
kg/km
VOLTAGE
kV
NO. OF CORES (PHASE + EARTH
+ CONTROL+ÜL)
NOMINAL CROSS  SECTIONAL AREA
mm2
CONDUCTOR DIAMETER
mm
MINIMUM OVERALL DIAMETER
mm
MAXIMUM OVERALL DIAMETER
mm
MAXIMUM TENSILE LOAD
N
NOMINAL WEIGHT
kg/km
Phase N Conductor Earth Conductor Control Conductor
3.6/6 3+3+3+ÜL 25 25/3E 2.5ST 6/8 45/4 48/8 1125 2960
3.6/6 3+3+3+ÜL 35 25/3E 2.5ST 7/8 46/9 50/4 1575 3340
3.6/6 3+3+3+ÜL 50 25/3E 2.5ST 9/4 50 53/6 2250 3990
3.6/6 3+3+3+ÜL 70 35/3E 2.5ST 11/2 55/6 59/4 3150 5180
3.6/6 3+3+3+ÜL 95 50/3E 2.5ST 12/7 59/9 63/9 4275 6370
3.6/6 3+3+3+ÜL 120 70/3E 2.5ST 14/4 64 68/4 5400 7730
6/10 3+3+3+ÜL 25 25/3E 2.5ST 6/8 45/4 49/4 1125 3000
6/10 3+3+3+ÜL 35 25/3E 2.5ST 7/8 46/9 51 1575 3380
6/10 3+3+3+ÜL 50 25/3E 2.5ST 9/4 50 54/2 2250 4030
6/10 3+3+3+ÜL 70 35/3E 2.5ST 11/2 55/6 60 3150 5220
6/10 3+3+3+ÜL 95 50/3E 2.5ST 12/7 59/9 64/5 4275 6410
6/10 3+3+3+ÜL 120 70/3E 2.5ST 14/4 64 69/1 5400 7770

CURRENT CARRYING CAPACITY

NOMINAL CROSS SECTIONAL AREA
mm2
LAYING ON THE FLOOR
Amps
FREE IN AIR
Amps
REELED
Amps
NOMINAL CROSS SECTIONAL AREA
mm2
LAYING ON THE FLOOR
Amps
FREE IN AIR
Amps
REELED
Amps
1 Layer 2 Layer 3 Layer 4 Layer 5 Layer 6 Layer 7 Layer
25 131 138 105 80 64 55 50 35 35
35 162 170 130 99 79 68 62 44 44
50 202 212 162 123 99 85 77 55 55
70 250 263 200 153 123 105 95 68 68
95 301 316 241 184 147 126 114 81 81
120 352 370 282 215 172 148 134 95 95
 Ambient temperature of 30°C

VOLTAGE DROP

NOMINAL CROSS SECTIONAL AREA
mm2
POWER FACTOR
NOMINAL CROSS SECTIONAL AREA
mm2
POWER FACTOR
0/7 0/8 0/9 1
25 1/29 1/45 1/6 1/71
35 0/95 1/06 1/16 1/23
50 0/69 0/77 0/83 0/87
70 0/51 0/56 0/6 0/61
95 0/41 0/45 0/47 0/47
120 0/34 0/36 0/38 0/36

DE-RATING FACTORS

 For AMBIENT TEMPERATURE other than 30°C (DE-RATING FACTOR at 30°C = 1)
AMBIENT TEMPERATURE 15ºC 20ºC 25ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
AMBIENT TEMPERATURE 15ºC 20ºC 25ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
DE-RATING FACTOR 1/12 1/08 1/04 0/96 0/91 0/87 0/82 0/76 0/71