این کابل برای نصب ثابت در ساختمان، در هوای آزاد، در زمین و در آب استفاده میشود
STANDARDS
IEC 60502-1, VDE 0276-603, HD 603, IEC 60228 Flame retardant according to IEC/EN 60332-1-2

این کابل برای نصب ثابت در ساختمان، در هوای آزاد، در زمین و در آب استفاده میشود
IEC 60502-1, VDE 0276-603, HD 603, IEC 60228 Flame retardant according to IEC/EN 60332-1-2
IEC 60502-1, VDE 0276-603, HD 603, IEC 60228 Flame retardant according to IEC/EN 60332-1-2
Voltage Rating Uo/U : 0.6/1kV
Operating Temperature : Operating: -5°C to +70°C
| Conductor : | RE: Class 1 solid aluminium-circular or circular compacted RM: Class 2 stranded SM: Class 2 sector - shaped SE: Class 1 solid sector - shaped or stranded (available upon request) |
|||
| Insulation : | PVC (Polyvinyl Chloride) | |||
| Sheath : | PVC (Polyvinyl Chloride) | |||
| NAYY-J: | 1 core: Green/ Yellow 3 core: Green/ Yellow Blue Black 4 core: Yellow Red Black Green/ Yellow 5 core: Yellow Red Black Blue Green/ Yellow |
||
| NAYY-O: | 1 core: Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/ Yellow |
||
| Sheath Colour : | Black | ||
NAYY-J
NAYY-J
| NO. OF CORES | CONDUCTOR TYPE | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL THICKNESS OF INSULATION mm |
FIXED INSTALLATION BENDING RADIUS mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL DIAMETER mm |
NOMINAL WEIGHT kg/km |
|---|---|---|---|---|---|---|---|
| NO. OF CORES | CONDUCTOR TYPE | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL THICKNESS OF INSULATION mm |
FIXED INSTALLATION BENDING RADIUS mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL DIAMETER mm |
NOMINAL WEIGHT kg/km |
| 1 | RE | 16 | 1 | 158 | 1/8 | 10/5 | 145 |
| 1 | RE | 25 | 1/2 | 180 | 1/8 | 12 | 195 |
| 1 | RE | 35 | 1/2 | 203 | 1/8 | 13/5 | 255 |
| 1 | RM | 50 | 1/4 | 231 | 1/8 | 15/4 | 298 |
| 1 | RM | 70 | 1/4 | 255 | 1/8 | 17 | 383 |
| 1 | RM | 95 | 1/6 | 285 | 1/8 | 19 | 490 |
| 1 | RM | 120 | 1/6 | 300 | 1/8 | 20 | 575 |
| 1 | RM | 150 | 1/8 | 330 | 1/8 | 22 | 695 |
| 1 | RM | 185 | 2 | 375 | 1/8 | 25 | 845 |
| 1 | RM | 240 | 2/2 | 420 | 1/8 | 28 | 1100 |
| 1 | RM | 300 | 2/4 | 450 | 1/9 | 30 | 1379 |
| 1 | RM | 400 | 2/6 | 510 | 2 | 34 | 1615 |
| 1 | RM | 500 | 2/8 | 555 | 2/1 | 37 | 2015 |
| 1 | RM | 630 | 2/8 | 645 | 2/2 | 43 | 2472 |
| 3 | SM | 300 | 2/4 | 708 | 3 | 59 | 4500 |
| 4 | RE | 6 | 1 | 204 | 1/8 | 17 | 377 |
| 4 | RE | 10 | 1 | 285 | 1/8 | 19 | 470 |
| 4 | RE | 16 | 1/2 | 288 | 1/8 | 24 | 750 |
| 4 | RE | 25 | 1/2 | 300 | 1/8 | 25 | 950 |
| NO. OF CORES | CONDUCTOR TYPE | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL THICKNESS OF INSULATION mm |
FIXED INSTALLATION BENDING RADIUS mm |
NOMINAL THICKNESS OF SHEATH mm |
NOMINAL DIAMETER mm |
NOMINAL WEIGHT kg/km |
|---|---|---|---|---|---|---|---|
| 4 | RE | 35 | 1/2 | 354 | 1/8 | 28/1 | 1120 |
| 4 | SM | 50 | 1/4 | 354 | 1/9 | 29/5 | 1151 |
| 4 | SM | 70 | 1/4 | 420 | 2/1 | 33/4 | 1549 |
| 4 | SM | 95 | 1/6 | 468 | 2/2 | 39 | 2030 |
| 4 | SM | 120 | 1/6 | 516 | 2/4 | 43 | 2400 |
| 4 | SM | 150 | 1/8 | 552 | 2/5 | 46 | 3030 |
| 4 | SM | 185 | 2 | 612 | 2/7 | 51 | 3650 |
| 4 | SM | 240 | 2/2 | 696 | 2/9 | 58 | 4800 |
| 4 | SM | 300 | 2/4 | 786 | 3 | 65/5 | 5685 |
| 5 | RE | 10 | 1 | 232 | 1/8 | 19/3 | 585 |
| 5 | RE | 16 | 1 | 262 | 1/8 | 21/8 | 938 |
| 5 | RE | 25 | 1/2 | 325 | 1/8 | 27/1 | 1188 |
| 5 | RE | 35 | 1/2 | 362 | 1/8 | 30/2 | 1375 |
| 5 | RM | 50 | 1/4 | 432 | 1/8 | 36/2 | 1720 |
| 5 | RM | 70 | 1/4 | 492 | 2/1 | 44 | 2240 |
| 5 | RM | 95 | 1/6 | 564 | 2/1 | 47 | 3060 |
| 5 | RM | 120 | 1/6 | 612 | 2/4 | 53 | 3580 |
| 5 | RM | 150 | 1/8 | 672 | 2/5 | 56 | 4400 |
| 5 | RM | 185 | 2 | 804 | 2/7 | 59 | 5481 |
| 5 | RM | 240 | 2/2 | 852 | 2/9 | 71 | 7000 |