SepehranCable.COM| خرید سیم و کابل سپهران کابل

Product Image

APPLICATION

STANDARDS

EN 50525-2-11 Flame Retardant according to IEC/EN 60332-1-2

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V

Temperature Rating : Flexed: +5°C to +70°C

Minimum Bending Radius : Fixed: 8 x overall diameter

CONSTRUCTION

Conductor : Class 5 flexible copper conductor
Insulation : PVC (Polyvinyl Chloride)
Sheath: PVC (Polyvinyl Chloride)
Core Identification : 2 core: Blue     Black
3 core: Yellow      Red      Black
4 core: Yellow      Red      Black      Blue
5 core: Yellow      Red      Black      Blue      Green/ Yellow
Sheath Colour : Black          ○ White

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS

NO. OF CORES NOMINAL CROSS
 SECTIONAL AREA
mm2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OVERALL
DIAMETER
mm
NOMINAL
WEIGHT
kg/km
NO. OF CORES NOMINAL CROSS
 SECTIONAL AREA
mm2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OVERALL
DIAMETER
mm
NOMINAL
WEIGHT
kg/km
2 0/75 0/6 6/3 57
2 1 0/6 6/6 65
2 1/5 0/7 7/4 84
2 2/5 0/8 9/1 130
3 0/75 0/6 6/7 68
3 1 0/6 7 78
3 1/5 0/7 8/1 108
3 2/5 0/8 9/9 163
3 4 0/8 11/3 227
4 0/75 0/6 7/3 82
4 1 0/6 7/9 100
4 1/5 0/7 9 134
4 2/5 0/8 10/8 201
5 0/75 0/6 8/1 102
5 1 0/6 8/6 120
5 1/5 0/7 10 166

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS
SECTIONAL AREA
mm2
MAXIMUM DIAMETER OF WIRES IN CONDUCTOR
mm
MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C
ohms/km
NOMINAL CROSS
SECTIONAL AREA
mm2
MAXIMUM DIAMETER OF WIRES IN CONDUCTOR
mm
MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C
ohms/km
Plain Wires
0/75 0/21 26
1 0/21 19/5
1/5 0/26 13/3
2/5 0/26 7/98
4 0/31 4/95

SepehranCable.COM| خرید سیم و کابل سپهران کابل

ELECTRICAL

Current Carrying Capacity and Mass Supportable

NOMINAL CROSS
SECTIONAL AREA
mm
CURRENT CARRYING CAPACITY
Amps
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CORD
Kg
NOMINAL CROSS
SECTIONAL AREA
mm
CURRENT CARRYING CAPACITY
Amps
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CORD
Kg
Single-Phase AC Three-Phase AC
0/75 6 6 3
1 10 10 5
1/5 16 16 5
2/5 25 20 5
4 32 25 5

VOLTAGE DROP

NOMINAL CROSS SECTIONAL AREA
mm2
DC OR SINGLE-PHASE AC
mV/A/m
THREE-PHASE AC
mV/A/m
NOMINAL CROSS SECTIONAL AREA
mm2
DC OR SINGLE-PHASE AC
mV/A/m
THREE-PHASE AC
mV/A/m
0/75 62 54
1 46 40
1/5 32 27
2/5 19 16
4 12 10

Conductor operating temperature: 60ºC

DE-RATING FACTORS

De-Rating Factor for Ambient Temperature 60ºC Thermoplastic or Therm

AIR TEMPERATURE 35ºC 40ºC 45ºC 50ºC 55ºC
AIR TEMPERATURE 35ºC 40ºC 45ºC 50ºC 55ºC
DE-RATING FACTOR 0.91 0.82 0.71 0/58 0/41