APPLICATION

نصب در دیوارها، روی تخته ها و کانال ها یا تعبیه در گچ. برای تاسیساتی که در آن ها آتش سوزی، انتشار دود و گازهای سمی خطر بالقوه ای برای زندگی و تجهیزات ایجاد می کند.

STANDARDS

BS7211, EN 60228 Flame Retardant according to BS EN/IEC 60332-1-2 Low Smoke Halogen Free according to IEC/EN 60754-1/2, IEC/EN 61034-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V

Temperature Rating : +5°C to +70°C

Minimum Bending Radius : 3 x overall diameter

CONSTRUCTION

Conductor : 1mm2 to 2.5mm2: Class 1 solid conductor 4mm2 to 10mm2: Class 2 stranded conductor

Circuit Protection Conductor (Earth) : 1mm² to 2.5mm²: Class 1 solid copper conductor 4mm² to 16mm²: Class 2 stranded copper conductor

Insulation :XLPE (Cross-Linked Polyethylene)

Sheath :LSZH (Low Smoke Zero Halogen)

Insulation Colour :2 core: Blue Brown 3 core: Brown Black Grey

Sheath Colour : White

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS


NO. OF CORES CONDUCTOR CLASS NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL THICKNESS OF SHEATH
mm
NOMINAL OVERALL DIMENSIONS
mm
NO. OF CORES CONDUCTOR CLASS NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL THICKNESS OF SHEATH
mm
NOMINAL OVERALL DIMENSIONS
mm
2 1 1 0/6 0/9 4.8 x 8.4
2 1 1/5 0/7 0/9 4.8 x 9.2
2 1 2/5 0/8 1 5.7 x 10.5
2 2 4 0/8 1 6.1 x 11.7
2 2 6 0/8 1/1 6.9 x 13.6
2 2 10 1 1/2 8.1 x 16.2
3 1 1 0/6 0/9 4.7 x 11
3 1 1/5 0/7 0/9 4.9 x 11.8
3 1 2/5 0/8 1 5.6 x 13.3
3 2 4 0/8 1 6.2 x 15.7

CONDUCTORS

Class 1 Copper Conductor for Single and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/km
NOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/km
Plain Wires
1 18/1
1/5 12/1
2/5 7/41
4 4/61
6 3/08
10 1/83

SepehranCable.COM| خرید سیم و کابل سپهران کابل

ELECTRICAL

Current Carrying Capacity

NOMINAL CROSS SECTIONAL AREA
mm2
REFERENCE METHOD A (IN CONDUIT IN WALL)
Amps
REFERENCE METHOD C* (CLIPPED DIRECT)
Amps
VOLTAGE DROP
mv/A/m
NOMINAL CROSS SECTIONAL AREA
mm2
REFERENCE METHOD A (IN CONDUIT IN WALL)
Amps
REFERENCE METHOD C* (CLIPPED DIRECT)
Amps
VOLTAGE DROP
mv/A/m
1 11/5 16 44
1/5 14/5 20 29
2/5 20 27 18
4 26 37 11
6 32 47 7/3
10 44 64 4/4
16 57 85 2/8