SepehranCable.COM| خرید سیم و کابل سپهران کابل

Product Image

APPLICATION

For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Examples of use include supplying mobile power units, UPS installations, stage lighting and audio visual equipment. This cable will withstand medium mechanical stresses and is suitable for both installation indoors and outdoors

STANDARDS

EN 50525-3-21, HD 22-13, CEI 20-19 Part 13, EN 60228 Flame Retardant according to IEC/EN 60332-3-10

CHARACTERISTICS

Voltage Rating Uo/U : 450/750V Suitable for 1kV in fixed application

Temperature Rating : Fixed: -20°C to +90°C Flexed: -5°C to +50°C

Minimum Bending Radius : Fixed: 4 x overall diameter Flexed: 6 x overall diameter

CONSTRUCTION

Insulation :EPR (Ethylene Propylene Rubber)

Conductor : Class 5 flexible copper conductor

Sheath :PCP (Polychloroprene)

Core Identification :1 core: Black 2 core: Blue Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/ Yellow

Sheath Colour : Black

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA mm2 NOMINAL OVERALL DIAMETER mm NOMINAL WEIGHT kg/km A2 GLANDS Brass A2PL GLAND Plastic
1 1.5 6.4 63 - -
1 2.5 7.1 76 - -
1 4 8.1 107 20S 20
1 6 8.85 140 20S 20
1 10 10.7 213 20S 20
1 16 12.1 291 20 25
1 25 14.25 415 25 25
1 35 16.1 539 25 25
1 50 18.55 740 25 32
1 70 20.95 989 32 32
1 95 23.4 1,290 32 40
1 120 25.7 1,592 40 40
1 150 28.3 1,957 40 40
1 185 31 2,350 50S 50
1 240 34.45 3,099 50 63
1 300 37.7 3,687 50 -
1 400 42.1 4,850 63S -
1 500 46.65 5,998 63 -
2 1 8.85 112 - -
2 1.5 9.75 135 20S 20

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS (CONTINUED)

NO. OF CORES NOMINAL CROSS SECTIONAL AREA mm2 NOMINAL OVERALL DIAMETER mm NOMINAL WEIGHT kg/km A2 GLANDS Brass A2PL GLAND Plastic
2 2.5 11.65 190 20 25
2 4 13.45 255 25 -
2 6 14.95 335 25 -
2 10 20.15 590 32 -
2 16 22.95 821 32 -
2 25 27.5 1,172 40 -
3 1 9.5 125 - -
3 1.5 10.55 129 20 20
3 2.5 12.45 250 25 25
3 4 14.45 330 25 -
3 6 16.05 440 25 -
3 10 21.65 800 32 -
3 16 24.7 1,150 40 -
3 25 29.55 1,680 50S -
3 35 33.2 2,170 50S -
4 1 10.55 170 20S -
4 1.5 11.65 196 20 25
4 2.5 13.8 275 25 25
4 4 15.95 388 25 25
4 6 17.85 515 32 32

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS (CONTINUED)

NO. OF CORES NOMINAL CROSS SECTIONAL AREA mm2 NOMINAL OVERALL DIAMETER mm NOMINAL WEIGHT kg/km A2 GLANDS Brass A2PL GLAND Plastic
4 10 23.7 882 40 40
4 16 26.95 1,234 40 40
4 25 32.75 1,811 50S 50
4 35 36.8 2,365 50 63
4 50 42.6 3,212 63S -
4 70 48.35 4,320 63 -
4 95 54.7 5,572 73S -
4 120 59.5 6,930 75 -
4 150 65.5 8,419 - -
4 185 72 10,165 - -
4 240 81.5 13,420 - -
5 1 11.65 205 20 -
5 1.5 12.8 242 25 25
5 2.5 15.15 341 25 25
5 4 17.75 495 32 32
5 6 19.85 642 32 32
5 10 26 1,090 40 40
5 16 29.85 1,534 50S 50
5 25 36.2 2,291 50 63
5 35 39.5 2,700 - -

SepehranCable.COM| خرید سیم و کابل سپهران کابل

DIMENSIONS (CONTINUED)

NO. OF CORES NOMINAL CROSS SECTIONAL AREA mm2 NOMINAL OVERALL DIAMETER mm NOMINAL WEIGHT kg/km A2 GLANDS Brass A2PL GLAND Plastic
5 50 44.2 3,730 63S -
5 70 50.4 5,022 - -
5 95 56.2 6,520 - -
5 120 64.1 8,080 - -
5 150 70.1 8,660 - -
7 1.5 16.7 355 25 32
12 1.5 20 660 32 32
19 1.5 27.5 788 40 40
27 1.5 31.5 1,077 40 40
37 1.5 36.5 1,358 50S 50

SepehranCable.COM| خرید سیم و کابل سپهران کابل

ELECTRICAL

 

Current Carrying Capacity and Mass Supportable

NOMINAL CROSS
SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
Amps
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE
NOMINAL CROSS
SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
Amps
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE
Single-Phase AC Three-Phase
 AC
1 10 10 5
1/5 16 16 5
2/5 25 20 5

Voltage Drop

NOMINAL CROSS
SECTIONAL AREA
mm2
DC OR SINGLE-PHASE AC
mV/A/m
THREE-PHASE AC
mV/A/m
NOMINAL CROSS
SECTIONAL AREA
mm2
DC OR SINGLE-PHASE AC
mV/A/m
THREE-PHASE AC
mV/A/m
1 46 40
1/5 32 27
2/5 19 16
 

Conductor operating temperature: 60ºC
Note
*The tabulated values above are for 60°C thermoplastic or thermosetting insulated flexible cables and for other types of flexible cable they are to be multiplied by the
following factors
For 90°C thermoplastic or thermosetting insulated 1.09
150°C 1.31

185°C glass fibre 1.43