APPLICATION
STANDARDS
BS 7846-F120 Fire Resistant to: BS 8491-120 mins, BS 6387 CAT CWZ, BS 8519 Cat3 Flame Retardant to: IEC 60332-3 Cat C, IEC 60332-1-2 Low Smoke Zero Halogen to: IEC 60754-1/2, IEC 61034-1/2
CHARACTERISTICS
Voltage Rating Uo/U : 0.6/1kV
Operating Temperature : -20ºC to +90ºC
Minimum Bending Radius : During Installation: 8 x overall diameter
CONSTRUCTION
| Conductor : | Class 2 stranded copper | ||
| Fire Barrier | MGT (Mica Glass Tape) | ||
| Insulation : | XLPE (Cross-Linked Polyethylene) | ||
| Inner Barrier : | Glass Tape | ||
| Bedding | LSZH (Low Smoke Zero Halogen) | ||
| Armour | SWA (Galvanised Steel Wire Armour) | ||
| Outr Sheath : | Glass Tape | ||
| Sheath | LSZH (Low Smoke Zero Halogen) | ||
| Core Identification : | 2 core : Brown Blue 3 core: Brown Black Grey 4 core: Brown Black Grey Blue 5 core: B Brown Black Grey Blue Green/ Yellow |
||
| Sheath Colour : | Black | ||