Medium voltage power cables with additional waterblocking properties for distribution networks and generation units, suitable for external installation including in direct in ground and in buried cable ducts. UV Resistant.
SepehranCable.COM| خرید سیم و کابل سپهران کابل

APPLICATION
STANDARDS
IEC 60502-2, IEC 60228, UV Resistant: ISO 4892-3 Abrasion and Tear Resistant: EN 60229-4.1 Impact rated to: AG2 EN 60364-5.51
CHARACTERISTICS
Voltage Rating Uo/U(Um) : 6/10 (12)kV
Test Voltage: 21kV AC 50Hz (5 mins)
Temperature Rating : -20°C to +60°C Permissible Conductor Operating Temperature: +90°C Permissible Short Circuit Temperature up to 5 sec: 250°C
Minimum Bending Radius : 15 x overall diameter
CONSTRUCTION
Conductor : Class 2 Stranded Aluminium
Conductor Screen:Semi-conductive material
Insulation :XLPE (Cross-Linked Polyethylene)
Insulation Screen:Semi-conductive material (bonded)
Screen :Copper wires and copper tape
Outer Sheath:MDPE (Medium Density Polyethylene)
Sheath Colour : Red Black