This cable is used for connection of electrical appliances without mechanical stress at increased environmental temperatures, for example in steelworks, but also at low temperatures. Insulation and sheath are resistant to most oils, acids, lyes and oxidants.
SepehranCable.COM| خرید سیم و کابل سپهران کابل
APPLICATION
STANDARDS
VDE 0482-332-1-2 Fire Retardant according to IEC 60332-1-2
CHARACTERISTICS
Voltage Rating Uo/U : 300/500V
Temperature Rating : Fixed: -60ºC to +180ºC
Minimum Bending Radius : Fixed: 6 x overall diameter Flexed: 15 x overall diameter
CONSTRUCTION
| Conductor : | Class 5 flexible stranded tinned copper | |
| Insulation : | Silicone Rubber | |
| Outer Sheath | Silicone Rubber | |
| Core Identification : | 3 cores: Green/ Yellow Blue Brown 4 cores: Green/ Yellow Blue Black Grey 5 cores: Green/ Yellow Blue Brown Black Grey More than 5 cores: Black numebered + Green/ Yellow |
|
| Sheath Colour | Red | |