VDE 0250 Part 812, VDE 0295, EN 60228 Flame Retardant according to IEC/EN 60332-1-2
STANDARDS
APPLICATION
Heavy duty tough rubber flexible cable for dynamic or static applications. It is suitable for installation inside or outside in dry, damp, wet and in hazardous environments. The overall screen provides a high level of electrical safety with EMC protection and makes the cable especially suitable for frequency converter controlled drives. This cable can be permanently submersed in water (fresh, salt, waste, storm, oily, sewage contaminated) to a depth of 100 metres. Suitable for indoor and outdoor applications.
CHARACTERISTICS
Voltage Rating Uo/U : 0.6/1kV
Test Voltage : 3kV Max AC Voltage: 0.7/1.2kV Max DC Voltage: 1.8kV
Temperature Range : Maximum Short Circuit Temperature: 250°C Static Condition: -40°C to +80°C Mobile Condition: -25°C to +80°C
Minimum Bending Radius : Fixed: 4 x overall diameter Flexed: 5 x overall diameter
CONSTRUCTION
| Phase Conductor : | Class 5 tinned copper conductor | |
| Earth Conductor : | Class 5 tinned copper conductor | |
| Insulation : | Rubber compound | |
| Screen : | TCWB (Tinned Copper Wire Braid) | |
| Inner Sheath : | Rubber compound | |
| Outer Sheath : | Rubber compound | |
| Sheath Colour : | Yellow | |
DIMENSIONS
| NO. OF CORES (PHASE + EARTH) |
NOMINAL CROSS SECTIONAL AREA mm2 |
CONDUCTOR DIAMETER mm |
MINIMUM OVERALL DIAMETER mm |
MAXIMUM OVERALL DIAMETER mm |
NOMINAL CROSS SECTIONAL AREA OF SCREEN mm2 |
NOMINAL WEIGHT kg/km |
MAXIMUM TENSILE LOAD | ||
| Phase Conductor | Earth Conductor | ||||||||
| 3 + 3 | 16 | 2.5E | 4/8 | 24/6 | 27/1 | 12 | 1170 | 720 | |
| 3 + 3 | 25 | 4E | 6/1 | 28/4 | 31/1 | 15 | 1650 | 1125 | |
| 3 + 3 | 35 | 16/3E | 7/2 | 31/9 | 33/6 | 22 | 2200 | 1575 | |
| 3 + 3 | 50 | 25/3E | 8/9 | 37/6 | 39/3 | 25 | 3110 | 2250 | |
| 3 + 3 | 70 | 35/3E | 10/6 | 41/4 | 44/2 | 30 | 3990 | 3150 | |
| 3 + 3 | 95 | 50/3E | 12/5 | 47/7 | 49/4 | 34 | 5080 | 4275 | |
| 3 + 3 | 120 | 70/3E | 14/2 | 51/6 | 53/4 | 38 | 6250 | 5400 | |
| 3 + 3 | 150 | 70/3E | 15/9 | 56/5 | 58/3 | 53 | 7450 | 6750 | |
| 3 + 3 | 185 | 95/3E | 17/7 | 62/4 | 64/4 | 59 | 9200 | 8325 | |
| 3 + 3 | 240 | 120/3E | 20/1 | 68/4 | 71/3 | 67 | 11700 | 10800 | |
CURRENT CARRYING CAPACITY
| NOMINAL CROSS SECTIONAL AREA mm2 |
LAYING ON THE FLOOR Amps |
FREE IN AIR Amps |
REELED Amps |
||||||
| 1 Layer | 2 Layer | 3 Layer | 4 Layer | 5 Layer | 6 Layer | 7 Layer | |||
| 16 | 99 | 104 | 79 | 60 | 49 | 42 | 38 | 27 | 22 |
| 25 | 131 | 138 | 105 | 80 | 64 | 55 | 50 | 35 | 29 |
| 35 | 162 | 170 | 130 | 99 | 79 | 68 | 62 | 44 | 36 |
| 50 | 202 | 212 | 162 | 123 | 99 | 85 | 77 | 55 | 44 |
| 70 | 250 | 263 | 200 | 153 | 123 | 105 | 95 | 68 | 55 |
| 95 | 301 | 316 | 241 | 184 | 147 | 126 | 114 | 81 | 66 |
| 120 | 352 | 370 | 282 | 215 | 172 | 148 | 134 | 95 | 77 |
| 150 | 404 | 424 | 323 | 246 | 198 | 170 | 154 | 109 | 89 |
| 185 | 461 | 484 | 369 | 281 | 226 | 194 | 175 | 124 | 101 |
| 240 | 528 | 554 | 422 | 322 | 259 | 222 | 201 | 143 | 116 |
VOLTAGE DROP
| NOMINAL CROSS SECTIONAL AREA mm2 |
POWER FACTOR | ||||||||
| 0/7 | 0/8 | 0/9 | 1 | ||||||
| 16 | 1/96 | 2/21 | 2/45 | 2/66 | |||||
| 25 | 1/29 | 1/45 | 1/6 | 1/71 | |||||
| 35 | 0/95 | 1/06 | 1/16 | 1/23 | |||||
| 50 | 0/69 | 0/77 | 0/83 | 0/87 | |||||
| 70 | 0/51 | 0/56 | 0/6 | 0/61 | |||||
| 95 | 0/41 | 0/45 | 0/47 | 0/47 | |||||
| 120 | 0/34 | 0/36 | 0/38 | 0/36 | |||||
| 150 | 0/29 | 0/31 | 0/32 | 0/29 | |||||
| 185 | 0/25 | 0/27 | 0/27 | 0/24 | |||||
| 240 | 0/21 | 0/22 | 0/21 | 0/18 | |||||
DE-RATING FACTORS
| AMBIENT TEMPERATURE | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC | 50ºC | 55ºC | 60ºC |
| DE-RATING FACTOR | 1/08 | 1/04 | 1 | 0/96 | 0/91 | 0/87 | 0/82 | 0/76 | 0/71 |