Standard Fire Resistant Cable

APPLICATION

Standard fire resistant cables for use primarily in fire detection, fire alarm, voice alarm, and emergency lighting circuits. These cables are designed to continue to operate for a period of time in a fire situation. ‘Standard’ fire resistance is recommended for general use.

STANDARDS

BS 7629-1, BS 5839-1 Low Smoke Zero Halogen to IEC/EN 60754-1/2, IEC/EN 61034-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V

Temperature Rating : -40°C to +90°C

Minimum Bending Radius : 6 x overall diameter

CONSTRUCTION

Conductor : 1.5mm2 - 2.5mm2: Class 1 solid Copper
4mm2 and over: Class 2 stranded Copper
Insulation : High performance fire resistant silicone rubber
Overall Screen: Al/PET (Aluminium/Polyester Tape) 
Circuit Protective Conducto Tinned copper
Outer Sheath : LSZH (Low Smoke Zero Halogen)
Core Identification : 2 core: Blue    Black
3 core: Yellow     Red     Black+ Bare Earth
4 core: Yellow     Red     Black     Blue
Sheath Colour : Red              White

DIMENSIONS

NO. OF CORES NOMINAL CROSS
 SECTIONAL AREA
mm2
CONDUCTOR TYPE NOMINAL THICKNESS OF INSULATION
mm
NOMINAL THICKNESS OF SHEATH
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
1 2/5 RE 0/8 1/4 6/15 62
1 4 RE 1 1/4 7/5 85
1 6 RE 1 1/4 7/5 108
1 10 RM 1 1/4 8/6 155
1 16 RM 1 1/4 9/6 218
1 25 RM 1/2 1/4 11/1 318
1 35 RM 1/2 1/4 12/1 414
1 50 RM 1/4 1/4 13/7 552
1 70 RM 1/4 1/4 15/5 750
1 95 RM 1/6 1/5 17/6 1020
1 120 RM 1/6 1/6 19/3 1259

CONDUCTORS

Class 1 Solid Plain Conductor

NO. OF
CORES
NOMINAL CROSS SECTIONAL AREA
mm2
EARTH WIRE CONSTRUCTION
n° /mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 1/5 1/1.38 8 95
2 2/5 1/1.75 9/4 130
2 4 7/0.85 11/5 200
3 1/5 1/1.38 8/5 115
3 2/5 1/1.75 10 170
3 4 7/0.85 12/2 260
4 1/5 1/1.38 9/4 140
4 2/5 1/1.75 11 210
4 4 7/0.85 13/5 330

ELECTRICAL CHARACTERISTICS

NOMINAL CROSS
SECTIONAL AREA
mm2
CONDUCTOR RESISTANCE
AT 20ºC
Ω/km
INSULATION RESISTANCE
AT 20ºC
MΩXkm
NOMINAL CAPACITANCE
pF/m
Core / Core Core / Screen
1 18/1 300 100 170
1/5 12/1 300 110 190
2/5 7/41 300 130 220
4 4/61 300 160 270

CURRENT CARRYING CAPACITY

Clipped Direct

NOMINAL CROSS
SECTIONAL AREA
mm2
CURRENT RATING
Amps
2 Core 3 and 4 Core
1 19 17
1/5 24 22
2/5 33 30
4 45 40
 

In Conduit or in Cable Tray

NOMINAL CROSS
SECTIONAL AREA
mm2
CURRENT RATING
Amps
2 Core 3 and 4 Core
1 17 15
1/5 22 19/5
2/5 30 26
4 40 35
 

VOLTAGE DROP

Clipped Direct

NOMINAL CROSS
SECTIONAL AREA
mm2
VOLTAGE DROP
mV/A/m
2 Core 3 and 4 Core
1 45 39
1/5 30 26
2/5 18 15
4 11 10
 

In Conduit or in Cable Tray

NOMINAL CROSS
SECTIONAL AREA
mm2
VOLTAGE DROP
mV/A/m
2 Core 3 and 4 Core
1 45 39
1/5 30 26
2/5 18 15
4 11 10
 

DE-RATING FACTORS

For Air Temperature other than 30°C (DE-RATING FACTOR at 30°C = 1)

AMBIENT TEMPERATURE 25ºC 35ºC 40ºC 45ºC 50ºC 55ºC
DE-RATING FACTOR 1/04 0/95 0/9 0/85 0/8 0/74