BS 8436 LSZH Cable

APPLICATION

این کابل برای استفاده در دیوارها، پارتیشن ها و فضاهای خالی ساختمان که در آن خطر آسیب یا نفوذ میخ وجود دارد مناسب است به دلیل داشتن روکش LSZH مناسب برای نصب در فضاهایی است که انتشار دودهای سمی ناشی از آتش سوزی برای زندگی و تجهیزات مخاطره آمیز میباشد.

STANDARDS

BS 8436, Flame Retardant according to IEC/EN 60332-1-2 Low Smoke Halogen Free according to IEC/EN 60754-1/2, IEC/EN 61034-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V
Temperature Rating : Fixed: -25°C to +90°C     
Minimum Bending Radiu Fixed: 6 x overall diameter
 

CONSTRUCTION

Conductor : Class 2 stranded copper conductor
Class 1 solid copper conductor available on request
Insulation : XLPE (Cross-Linked Polyethylene)
Circuit Protective Conducto Tinned copper
Screen Tubed aluminium
Sheath : LSZH (Low Smoke Zero Halogen)
Sheath Colour : White
 

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 1 7/1 71
2 1/5 8 88
2 2/5 9 127
2 4 10/4 181
3 1 7/5 85
3 1/5 8/5 112
3 2/5 9/4 154
3 4 11/2 230
4 1 8/3 107
4 1/5 9/4 139
4 2/5 10/5 191
4 4 12/4 285
 

CONDUCTORS

Class 1 Solid Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM RESISTANCE
OF CONDUCTOR AT 20°C
ohms/km
1 18/1
1/5 12/1
2/5 7/41
4 4/61
 

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity and Voltage Drop

NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT RATING CLIPPED DIRECT)
Amps
Single Phase AC or DC Three Phase AC
1 15 13/5
1/5 19/5 17/5
2/5 27 24
4 36 32
 

VOLTAGE DROP

NOMINAL CROSS SECTIONAL AREA
mm2
DC
mV/A/m
SINGLE PHASE AC
mV/A/m
THREE PHASE AC
mV/A/m
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9/5

 Notes 1. The above current ratings are taken from Table 4D2 (maximum conductor operating temperature of 70°C) as required by the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52. However, these cables are capable of operating at 90°C in which case the higher current ratings of Table 4E2 can be used providing it has been ascertained that the equipment connected to the conductor is suitable for the higher conductor operating temperature. 2. Protective devices used for these cables shall be either Type B to BS EN 60898 or Type B RCBO to BS EN 61009-1. The protective devices shall have a maximum let through energy (l2t) of 42000A2s when used with 1.0mm2 or 1.5mm2 cable and 60000 A2s when used with 2.5mm2 or 4.0mm2 cable.

 

اطلاعات ارائه شده در این برگه ، صرفاً جهت راهنمایی مهندسان طراح سیستمهای برق و کاربران است . تمامی اطلاعات با حسن نیت ارائه شده و اعتقاد بر این است که در زمان انتشار صحیح بوده است . هنگام انتخاب تجهیزات جانبی کابل لطفاً توجه داشته باشید که ابعاد واقعی کابل ممکن است به دلیل شرایط تولید متفاوت باشد .
کارشناسان این شرکت با افتخار ، آماده ارائه هرگونه اطلاعات فنی و مهندسی تکمیلی در خصوص این کابل و یا سایر کابلهای مورد نیاز پروژه شما میباشند .