NA2XY Cable Aluminium XLPE PVC - 0.6/1kV

APPLICATION

برای نصب ثابت در ساختمان، در هوای آزاد، در زمین و در آب

STANDARDS

IEC 60502-1, VDE 0276-603 Flame retardant according to IEC/EN 60332-1-2

CHARACTERISTICS

Voltage Rating Uo/U (Um): 0.6/1 (1.2)kV
Nominal Voltage DC
(core-earth/core-core) : 1.8/1.8kV
Test Voltage : 4kV
Temperature Rating : Flexed: 5°C to +70°C
Fixed: -35°C to +70°C
Maximum Short Circuit Temperature: 250 °C (max 5 seconds)
Minimum Bend Radius: Single core: 15 x overall diameter
Multi core: 12 x overall diameter
 

CONSTRUCTION

Conductor : Class 2 stranded Aluminium conductor
Class 1 solid conductors available on request
Insulation : XLPE (Cross-Linked Polyethylene)
Sheath: PVC (Polyvinyl Chloride)
 

Core Identification

NA2XY-J: 3 core: Yellow     Red     Black
4 core: Yellow     Red     Black     Blue
NA2XY-O: 2 core: Blue    Black
3 core: Yellow     Red     Black
4 core: Yellow     Red     Black     Blue
Sheath Colour : Black
 

DIMENSIONS

NO. OF CORES NOMINAL CROSS
 SECTIONAL AREA
mm2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL THICKNESS OF SHEATH
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
Phase Conducto Earth Conductor
1 95 - 1/1 1/5 16/5 390
1 120 - 1/2 1/8 17/7 465
1 150 - 1/4 1/8 20/1 580
1 185 - 1/6 1/8 22/1 715
1 240 - 1/7 1/8 25 905
1 300 - 1/8 1/8 27/5 1120
1 400 - 2 1/9 31/4 1440
1 500 - 2/2 2 34/6 1770
1 630 - 2/4 - 37 2180
3 70 35 1/1 1/9 33 1450
3 95 50 1/1 2/1 37/3 1910
3 120 70 1/2 2.2 41/5 2410
3 150 70 1/4 2.3 49.0 3535
3 185 95 1/6 2.5 51 3810
3 240 120 1/7 2.7 58 4880
3 300 150 1.8 2/8 64/2 5610
4 16 16 0/9 1/8 22/4 675
4 25 16 0/9 1/8 26 910
4 35 16 0/9 1/8 28/7 1120
4 50 25 1 1.8 33 1475
4 70 35 1/1 1/9 38 1985
4 95 50 1/1 2/1 23 2580
4 120 70 1/2 2.2 47/2 3175
4 150 70 1/4 2.3 54/2 4035
4 185 95 1/6 2.5 59/4 4945
4 240 120 1/7 2/7 68/1 6425
4 300 150 1/8 2/8 75/1 7910
 

CONDUCTORS

Phase Conductor

NOMINAL CROSS SECTIONAL AREA mm2 MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km
16 1/91
25 1/2
35 0/868
50 0/641
70 0/443
95 0/32
120 0/253
150 0/206
185 0/164
240 0/125
300 0/1
400 0/0778
500 0/0605
630 0/0469
 

CURRENT CARRYING CAPACITY

NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
Amps
Phase Conductor In Ground In Air
Single Core Flat Single Core Triplex Multi-Core Single Core Flat Single Core Triplex Multi-Core
16 - - 85 - - 65
25 - - 111 - - 100
35 - - 132 - - 122
50 - - 157 - - 147
70 - - 195 - - 180
95 - 226 233 - 215 232
120 323 274 266 366 296 270
150 361 308 299 420 341 308
185 408 350 340 486 395 357
240 476 408 401 585 475 435
300 537 462 455 675 548 501
400 616 547 - 798 659 -
500 699 621 - 926 814 -
630 - 687 - - 822 -
 

اطلاعات ارائه شده در این برگه ، صرفاً جهت راهنمایی مهندسان طراح سیستمهای برق و کاربران است . تمامی اطلاعات با حسن نیت ارائه شده و اعتقاد بر این است که در زمان انتشار صحیح بوده است . هنگام انتخاب تجهیزات جانبی کابل لطفاً توجه داشته باشید که ابعاد واقعی کابل ممکن است به دلیل شرایط تولید متفاوت باشد .
کارشناسان این شرکت با افتخار ، آماده ارائه هرگونه اطلاعات فنی و مهندسی تکمیلی در خصوص این کابل و یا سایر کابلهای مورد نیاز پروژه شما میباشند .