BS 7846 F120 Armoured Fire Performance Power Cable

APPLICATION

These armoured fire performance power cables are fire resistant and designed for direct impact. Designed to meet the application of fire, direct impact and water jet as specified in BS 8491, making them suitable for use as 120 minute rated category 3 power cables according to BS 8519.

STANDARDS

BS 7846-F120 Fire Resistant to: BS 8491-120 mins, BS 6387 CAT CWZ, BS 8519 Cat3 Flame Retardant to: IEC 60332-3 Cat C, IEC 60332-1-2 Low Smoke Zero Halogen to: IEC 60754-1/2, IEC 61034-1/2 

CHARACTERISTICS

Voltage Rating Uo/U : 0.6/1kV

Operating Temperature : -20ºC to +90ºC

Minimum Bending Radius : During Installation: 8 x overall diameter

CONSTRUCTION

Conductor : Class 2 stranded copper
Fire Barrier MGT (Mica Glass Tape)  
Insulation : XLPE (Cross-Linked Polyethylene)
Inner Barrier : Glass Tape
Bedding LSZH (Low Smoke Zero Halogen)
Armour SWA (Galvanised Steel Wire Armour)
Outr Sheath : Glass Tape
Sheath LSZH (Low Smoke Zero Halogen) 
Core Identification : 2 core : Brown Blue
3 core: Brown Black Grey
4 core: Brown Black Grey Blue
5 core: B Brown Black Grey Blue Green/Yellow
Sheath Colour : Black

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
INSULATION RADIAL THICKNESS
mm
GALVANISED STEEL ARMOUR WIRE DIAMETER
mm
OUTER SHEATH RADIAL THICKNESS
mm
OUTER SHEATH DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 4 0/7 1/25 1/4 23/9 950
2 6 0/7 1/25 1/4 25/1 1100
2 10 0/7 1/25 1/5 26/4 1200
2 16 0/7 1/25 1/5 28/3 1400
2 25 0/9 1/25 1/6 31/4 1800
2 35 0/9 1/6 1/7 34/1 2250
3 4 0/7 1/25 1/4 23/4 950
3 6 0/7 1/25 1/4 24/7 1100
3 10 0/7 1/25 1/5 25/2 1200
3 16 0/7 1/25 1/6 27/4 1500
3 25 0/9 1/6 1/7 31/7 2000
3 35 0/9 1/6 1/8 34 2500
3 50 1 1/6 1/8 32/7 2750
3 70 1/1 1/6 1/9 36/4 3500
3 95 1/1 2 2/1 41 4750
3 120 1/2 2 2/2 44/5 5500
3 150 1/4 2/5 2/3 49/3 7000
3 185 1/6 2/5 2/4 53/4 8250
3 240 1/7 2/5 2/6 58/7 10500
3 300 1/8 2/5 2/7 63/7 12500
3 400 2 2/5 2/9 71/1 15500
4 4 0/7 1/25 1/4 24/7 1100
4 6 0/7 1/25 1/5 26/2 1200
4 10 0/7 1/25 1/5 27/8 1500
4 16 0/7 1/25 1/6 29/3 1700
4 25 0/9 1/6 1/7 34 2500
4 35 0/9 1/6 1/8 35/2 3000
4 50 1 1/6 1/9 36/6 3250
4 70 1/1 2 2/1 40/3 4500
4 95 1/1 2 2/2 44/6 5750
4 120 1/2 2/5 2/3 49/5 7250
4 150 1/4 2/5 2/4 54 8500
4 185 1/6 2/5 2/6 58/8 10500
4 240 1/7 2/5 2/7 64/8 13000
4 300 1/8 2/5 2/9 71/7 16000
4 400 2 3/15 3/2 82/5 21000
5 4 0/7 1/25 1/4 26/3 1200
5 6 0/7 1/25 1/5 27/9 1400
5 10 0/7 1/25 1/5 29/7 1700
5 16 0/7 1/25 1/6 32/2 2250

CONDUCTORS

NOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/km
4 4/61
6 3/08
10 1/83
16 1/15
25 0/727
35 0/524
50 0/387
70 0/268
95 0/193
120 0/153
150 0/124
185 0/0991
240 0/0754
300 0/0601
400 0/047

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

NOMINAL CROSS SECTIONAL AREA
mm²
2 CORE 3 AND 4 CORE
Single-Phase Three-Phase
Laid Direct
Amps
In Ducts
Amps
In Air
Amps
Laid Direct
Amps
In Ducts
Amps
In Air
Amps
4 65 53 55 55 45 47
6 81 67 70 69 56 59
10 109 89 95 92 75 82
16 141 115 126 119 96 107
25 183 148 164 152 124 140
35 219 178 202 182 149 172
50 259 211 244 217 177 209
70 317 260 306 266 218 263
95 381 313 378 319 263 324
120 433 357 437 363 300 346
150 485 401 499 409 338 430
185 547 455 576 458 382 495
240 632 527 680 529 442 584
300 708 592 775 592 496 672
400 799 669 892 667 570 766

Voltage Drop

NOMINAL CROSS SECTIONAL AREA
mm²
DC
M/V/A/M
SINGLE-PHASE AC
M/V/A/M
THREE-PHASE AC
M/V/A/M
4 12 12 10
6 7/9 7/9 6/8
10 4/7 4/7 4
16 2/9 2/9 2/5
25 1/85 1/9 1/65
35 1/35 1/35 1/15
50 0/98 1 0/87
70 0/97 0/69 0/6
95 0/49 0/52 0/45
120 0/39 0/42 0/37
150 0/31 0/35 0/3
185 0/25 0/29 0/26
240 0/195 0/24 0/21
300 0/155 0/21 0/185