VDE 0482-332-1-2 Fire Retardant according to: IEC 60332-1-2
STANDARDS
APPLICATION
This cable can be used for operation in ambient temperatures above 55 °C, for internal wiring of lamps, heating equipment and electrical appliances as well as for switching boxes and distribution boards.
CHARACTERISTICS
Voltage Rating Uo/U : 300/500V
Temperature Rating : Fixed: -60ºC to +180ºC
Minimum Bending Radius : Fixed: 6 x overall diameter Flexed: 15 x overall diameter
CONSTRUCTION
| Conductor : | Class 5 flexible stranded tinned copper | ||
| Insulation : | Silicone Rubber | ||
| Core Identification : | Green/Yellow Blue Black Brown Grey White Red |
||
DIMENSIONS
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
| 1 | 0/5 | 2/1 | 8/6 |
| 1 | 0/75 | 2/4 | 11 |
| 1 | 1 | 2/5 | 13/6 |
| 1 | 1/5 | 2/8 | 20/3 |
| 1 | 2/5 | 3/4 | 32 |
| 1 | 4 | 4/2 | 48/5 |
| 1 | 6 | 5/2 | 71 |
| 1 | 10 | 6/3 | 124 |
| 1 | 16 | 8 | 188 |
| 1 | 25 | 9/9 | 296 |
| 1 | 35 | 11/2 | 400 |
| 1 | 50 | 13/8 | 570 |
| 1 | 70 | 14/8 | 766 |
| 1 | 95 | 18/2 | 1030 |
| 1 | 120 | 18/8 | 1300 |
| 1 | 150 | 20/8 | 1563 |
| 1 | 185 | 23/3 | 1915 |
| 1 | 240 | 26/1 | 2440 |
| 1 | 300 | 28/9 | 3100 |
CURRENT CARRYING CAPACITY
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
CURRENT CARRYING CAPACITY IN FREE AIR AT 30°C A |
|
| 1 | 0/5 | 6 | |
| 1 | 0/75 | 15 | |
| 1 | 1 | 19 | |
| 1 | 1/5 | 24 | |
| 1 | 2/5 | 32 | |
| 1 | 4 | 42 | |
| 1 | 6 | 54 | |
| 1 | 10 | 73 | |
| 1 | 16 | 98 | |
| 1 | 25 | 129 | |
| 1 | 35 | 158 | |
| 1 | 50 | 198 | |
| 1 | 70 | 245 | |
| 1 | 95 | 292 | |
| 1 | 120 | 344 | |
| 1 | 150 | 391 | |
| 1 | 185 | 448 | |
| 1 | 240 | 528 | |
| 1 | 300 | 608 | |