VDE 0482-332-1-2 Fire Retardant according to IEC 60332-1-2
STANDARDS
APPLICATION
This cable is used for connection of mobile electrical appliances without mechanical stress at increased ambient temperatures, for example in steelworks, but also at low temperatures. Insulation and sheath are resistant to most oils, greases, acids, lyes and oxidants. For fixed installation in mechanical protected conduits. The cable is designed for use in EMCsensitive applications.
CHARACTERISTICS
Voltage Rating Uo/U : 300/500V
Temperature Rating : Fixed: -60ºC to +180ºC
Minimum Bending Radius : Fixed: 6 x overall diameter Flexed: 15 x overall diameter
CONSTRUCTION
| Conductor : | Class 5 flexible stranded tinned copper | |
| Insulation : | Silicone Rubber | |
| Inner Sheath | Silicone Rubber | |
| Screen | TCWB (Tinned Copper Wire Braid) | |
| Outer Sheath | Silicone Rubber | |
| Core Identification : | 3 cores: Green/Yellow Blue Brown 4 cores: Green/Yellow Blue Black Grey 5 cores: Green/Yellow Blue Brown Black Grey More than 5 cores: Black numebered + Green/Yellow |
|
| Sheath Colour | Red | |
DIMENSIONS
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
| 2 | 0/75 | 9/2 | 124 |
| 2 | 1 | 9/5 | 132 |
| 2 | 1/5 | 10/7 | 172 |
| 2 | 2/5 | 12/1 | 230 |
| 3 | 0/75 | 9/9 | 130 |
| 3 | 1 | 9/7 | 146 |
| 3 | 1/5 | 11/8 | 198 |
| 3 | 2/5 | 12/9 | 275 |
| 4 | 0/75 | 10/1 | 159 |
| 4 | 1 | 10/7 | 174 |
| 4 | 1/5 | 12/1 | 230 |
| 4 | 2/5 | 14/2 | 334 |
| 4 | 4 | 17/1 | 520 |
| 4 | 6 | 18/8 | 781 |
| 4 | 10 | 25/7 | 1294 |
| 4 | 16 | 28/4 | 1988 |
| 4 | 25 | 35 | 2995 |
| 5 | 0/75 | 10/9 | 177 |
| 5 | 1 | 11/6 | 203 |
| 5 | 1/5 | 13/3 | 276 |
| 5 | 2/5 | 15/6 | 394 |
| 5 | 4 | 19/4 | 592 |
| 7 | 0/75 | 11/6 | 214 |
| 7 | 1 | 12/1 | 247 |
| 7 | 1/5 | 14/3 | 342 |
| 7 | 2/5 | 16/9 | 488 |
| 12 | 1 | 15/2 | 454 |
| 12 | 1/5 | 19/6 | 371 |
| 18 | 1/5 | 20/9 | 720 |
| 24 | 1 | 24/2 | 526 |
| 25 | 1/5 | 27 | 791 |
CURRENT CARRYING CAPACITY
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
CURRENT CARRYING CAPACITY IN FREE AIR AT 30°C A |
|
| 2 | 0/75 | 12 | |
| 2 | 1 | 15 | |
| 2 | 1/5 | 18 | |
| 2 | 2/5 | 26 | |
| 3 | 0/75 | 12 | |
| 3 | 1 | 15 | |
| 3 | 1/5 | 18 | |
| 3 | 2/5 | 26 | |
| 4 | 0/75 | 12 | |
| 4 | 1 | 15 | |
| 4 | 1/5 | 18 | |
| 4 | 2/5 | 26 | |
| 4 | 4 | 34 | |
| 4 | 6 | 44 | |
| 4 | 10 | 61 | |
| 4 | 16 | 82 | |
| 4 | 25 | 108 | |
| 5 | 0/75 | 12 | |
| 5 | 1 | 15 | |
| 5 | 1/5 | 18 | |
| 5 | 2/5 | 26 | |
| 5 | 4 | 34 | |
| 7 | 0/75 | 12 | |
| 7 | 1 | 15 | |
| 7 | 1/5 | 18 | |
| 7 | 2/5 | 26 | |
| 12 | 1 | 15 | |
| 12 | 1/5 | 18 | |
| 18 | 1/5 | 18 | |
| 24 | 1 | 15 | |
| 25 | 1/5 | 18 | |