EN 50288-7, EN 50288-1, EN 60228 Flame Retardant to: IEC/EN 60332-1-2, IEC/EN 60332-3-24 Low Smoke Halogen Free to: IEC/EN 60754-1/2, IEC/EN 61034-2, UV Resistant to UL 1581-1200
APPLICATION
These cables are designed to connect electrical instrument circuits and provide communication services in and around process plants (e.g. petrochemical industry etc.). Pairs are individually shielded for enhanced signal security to prevent cross-talk within cable. Suitable for direct burial applications. For installations where fire, smoke emissions and toxic fumes create a potential risk to life and equipment
STANDARDS
CHARACTERISTICS
Voltage Rating Uo/U : 300V
Operating Temperature : Fixed: -40°C to +80°C Flexed: 0°C to +50°C
Minimum Bending Radius : 12 x overall diameter
CONSTRUCTION
Conductor : 0.5mm² - 0.75mm²: Class 5 flexible Copper 1mm² and above: Class 2 stranded CopperInsulation : XLPE (Cross-Linked Polyethylene)
Individual and Collective Screen Al/PET (Aluminium/Polyester Tape)
Drain Wire Tinned Copper
Inner Sheath : LSZH (Low Smoke Zero Halogen)
Armour SWA (Galvanised steel wires)
Outer Sheath LSZH (Low Smoke Zero Halogen) - UV Resistant
Core Identification : Pairs: White Black, numbered Triples: White Black Red
Outer Sheath Colour : BlueBlack
DIMENSIONS
| NO. OF PAIRS/TRIPLE | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL OVERALL DIAMETER mm | |
| 2P | 0/5 | 11/9 | |
| 2P | 0/75 | 12/9 | |
| 2P | 1 | 12/7 | |
| 2P | 1/5 | 15/2 | |
| 1T | 0/5 | 12/3 | |
| 1T | 0/75 | 13/4 | |
| 1T | 1 | 13/2 | |
| 1T | 1/5 | 15/9 | |
| 5P | 0/5 | 14 | |
| 5P | 0/75 | 15/4 | |
| 5P | 1 | 15/1 | |
| 5P | 1/5 | 18/5 | |
| 10P | 0/5 | 18 | |
| 10P | 0/75 | 20/6 | |
| 10P | 1 | 22 | |
| 10P | 1/5 | 26/1 | |
| 15P | 0/5 | 20/7 | |
| 15P | 0/75 | 23/1 | |
| 15P | 1 | 22/6 | |
| 15P | 1/5 | 29/5 | |
| 20P | 0/5 | 22/9 | |
| 20P | 0/75 | 26/3 | |
| 20P | 1 | 25/8 | |
| 20P | 1/5 | 33/5 | |
| 30P | 0/5 | 26/8 | |
| 30P | 0/75 | 30/1 | |
| 30P | 1 | 29/4 | |
| 30P | 1/5 | 38/4 | |
CONDUCTORS
| NOMINAL CROSS SECTIONAL AREA mm2 | MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20°C ohms/km | ||
| Class 2 | Class 5 | ||
| 0/5 | 36/36 | 39/39 | |
| 0/75 | 24/8 | 26/8 | |
| 1 | 18/3 | 19/7 | |
| 1/5 | 12/42 | 13/43 | |
| 2/5 | 7/56 | 8/05 | |
ELECTRICAL CHARACTERISTICS
| NOMINAL CROSS SECTIONAL AREA mm2 | MUTUAL CAPACITANCE pF/m | MINIMUM INSULATION RESISTANCE AT 20°C Gohms/km | MAXIMUM L/R RATIO μH/ohms |
| 0/5 | 115 | >10 | 25 |
| 0/75 | 115 | >10 | 25 |
| 1 | 115 | >10 | 25 |
| 1/5 | 120 | >10 | 40 |
| 2/5 | 120 | >10 | 65 |