N2XBH Cable

APPLICATION

The N2XBH cable can be used in refineries, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.

STANDARDS

DIN VDE 0276-604, TS HD 604.S1, IS 1516.1, IEC 60502-1 Flame retardant according to IEC 60332-3-24 Cat. C Low Smoke Zero Halogen according to IEC/EN 60754-1/2, IEC/ EN 61034-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 0.6/1kV

Test Voltage: 3.5kV

Temperature Rating : Maximum Operating: +90ºC Maximum Short-Circuit: +250°C

Minimum Bending Radius : 12 x overall diameter

CONSTRUCTION

Conductor : Class 2 Stranded copper

Insulation :XLPE (Cross-Linked Polyethylene)

Filler :PVC (Polyvinyl chloride)

Armour 1:SWA (Galvanised flat steel wire)

Armour 2:Galvanized steel tape

Outer Sheath :PVC (Polyvinyl chloride)

Core Identification :2 core: Blue Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/Yellow

Sheath Colour :Black

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
NOMINAL DIAMETER OF CONDUCTOR
mm
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL THICKNESS OF OUTER SHEATH
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 2/5 1/76 0/7 1/24 13 276
2 4 2/21 0/7 1/24 14 326
2 6 2/71 0/7 1/24 15 384
2 10 3/85 0/7 1/24 17 498
2 16 4/8 0/7 1/24 19 649
2 25 5/85 0/9 1/24 22 882
2 35 6/9 0/9 1/32 24 1113
2 50 8/1 1 1/4 27 1421
2 70 9/7 1/1 1/48 31 1899
2 95 11/4 1/1 1/64 35 2482
3 1/5 1/36 0/7 1/24 12 265
3 2/5 1/76 0/7 1/24 14 342
3 4 2/21 0/7 1/24 15 417
3 6 2/71 0/7 1/24 16 501
3 10 3/85 0/7 1/24 19 704
3 16 4/8 0/7 1/24 21 938
3 25 5/85 0/9 1/24 24 1315
3 35 6/9 0/9 1/32 26 1682
3 50 8/1 1 1/4 29 2176
3 70 9/7 1/1 1/48 34 2949
3 95 11/4 1/1 1/64 38 4004
3 120 12/65 1/2 1/72 42 5215
3 150 14/4 1/4 1/88 47 6413
3 185 15/75 1/6 2/04 51 7719
3 240 18/2 1/7 2/2 58 9961
3 16+10 4/8 0/7 1/24 21 1073
3 25+16 5/85 0/9 1/24 25 1511
3 35+16 6/9 0/9 1/32 27 1861
3 50+25 8/1 1 1/4 30 2377
3 70+35 9/7 1/1 1/56 35 3235
3 95+70 11/4 1/1 1/64 39 4634
3 120+70 12/65 1/2 1/8 44 5813
3 150+70 14/4 1/4 1/88 48 6888
3 185+95 15/75 1/6 2/04 52 8412
3 240+120 18/2 1/7 2/2 59 10679
4 1/5 1/36 0/7 1/24 13 309
4 2/5 1/76 0/7 1/24 14 369
4 4 2/21 0/7 1/24 16 469
4 6 2/71 0/7 1/24 17 577
4 10 3/85 0/7 1/24 20 821
4 16 4/8 0/7 1/24 22 1113
4 25 5/85 0/9 1/32 25 1593
4 35 6/9 0/9 1/4 28 2060
4 50 8/1 1 1/48 32 2637
4 70 9/7 1/1 1/56 36 3611
4 95 11/4 1/1 1/72 41 5355
4 120 12/65 1/2 1/88 46 6590
4 150 14/4 1/4 1/96 51 8096
4 185 15/75 1/6 2/12 56 9795
4 240 18/2 1/7 2/36 63 12585
5 1/5 1/36 0/7 1/24 14 368
5 2/5 1/76 0/7 1/24 15 432
5 4 2/21 0/7 1/24 17 543
5 6 2/71 0/7 1/24 18 679
5 10 3/85 0/7 1/24 21 981
5 16 4/8 0/7 1/24 24 1351
5 25 5/85 0/9 1/32 28 1960
5 35 6/9 0/9 1/4 31 2539
5 50 8/1 1 1/48 35 3333
5 70 9/7 1 1/48 39 4507
5 95 11/4 1/1 1/56 44 6038

ELECTRICAL CHARACTERISTICS

NOMINAL CROSS
SECTIONAL AREA mm2
CURRENT CARRYING CAPACITY
A
MAXIMUM CONDUCTOR
RESISTANCE AT 20°C Ω/km
IN CONDUIT IN AIR
1/5 31 24 12/1
2/5 40 31 7/41
4 52 41 4/61
6 65 53 3/08
10 87 72 1/83
16 113 96 1/15
25 146 130 0/727
35 176 160 0/524
50 208 195 0/387
70 256 247 0/268
95 307 305 0/193
120 349 355 0/153
150 391 407 0/124
185 442 469 0/0991
240 509 551 0/0754