Maximum Operating Voltage 300V
Temperature Rating : Fixed: -40°C to +70°C Flexing: -10°C to +50°C
Minimum Bending Radius : Fixed: 12 x overall diameter
Veriflex® Profibus cable for Fast-Connect, installed indoors in fixed and occasional flexing applications. A fieldbus standard that supports a wide variety of Profibus DP (Decentralized Peripherals) applications in automated manufacturing. Depending on bit rates, segment lengths of up to 1,200m can be achieved.
IEC 61158, EN 50170, CEI 20-37/7, CEI 20-38, Fire Retardant according to IEC/EN 60332-1 Low Smoke Zero Halogen according to IEC/EN 61034-1/2, IEC/EN 60754-1/2
Maximum Operating Voltage 300V
Temperature Rating : Fixed: -40°C to +70°C Flexing: -10°C to +50°C
Minimum Bending Radius : Fixed: 12 x overall diameter
| NO. OF PAIRS | NOMINAL CROSS SECTIONAL AREA mm2 | NOMINAL DIAMETER OF CONDUCTOR mm | NOMINAL DIAMETER OF INSULATION mm | NOMINAL OUTER DIAMETER OF INNER SHEATH mm | NOMINAL DIAMETER OF OUTER SHEATH mm | NOMINAL WEIGHT kg/km | |
| 1 | 0/35 | 0/64 | 2/5 | 5/5 | 7/9 | 76 | |
| MAX DC LOOP CONDUCTOR RESISTANCE Ω/km | MAXIMUM DC CONDUCTOR RESISTANCE Ω/km | CAPACITANCE AT 800 HZ nF/km | IMPEDANCE (3÷20 MHZ) Ω (± 10%) | MAXIMUM ATTENUATION dB/km | |||
| 9.6kHz | 38.4kHz | 4kHz | 16kHz | ||||
| 115 | 57/5 | 29 | 150 | 0/3 | 0/5 | 2/1 | 4 |
| DIELECTRIC STRENGTH kVac / 1 min | MINIMUM INSULATION RESISTANCE GΩ X KM | MAXIMUM INSTALLATION PULLING N | |||||
| Cond/Cond | Cond/Shield | ||||||
| 1/5 | 1/5 | 5 | 100 | ||||