APPLICATION

Veriflex steel wire braided flexible connecting cables for instrumentation and control equipment, for tooling machinery production lines, and in flexible applications for free movement without tensile load. Suitable for use in dry, moist and wet rooms. The galvanised steel wire braid serves as protection against mechanical traverse loads and acts as a magnetic screen against interference. These cables are not used for outdoor or underground installation.

STANDARDS

VDE 0207-363-3, VDE 0482-332-1-2, VDE 819-102 (TM54) Flame Retardant according to IEC/EN 60332-1-2

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V

Temperature Rating : Fixed: -40°C to +80°C Flexed: -5°C to +70°C

Minimum Bending Radius : Fixed: 4 x overall diameter Flexed: 12.5 x overall diameter

CONSTRUCTION

Conductor : Class 5 flexible plain copper

Insulation :PVC (Polyvinyl Chloride)

Inner Sheath :PVC (Polyvinyl Chloride)

Armour:GSWB (Galvanised Steel Wire Braid)

Sheath:PVC (Polyvinyl Chloride)

Core Identification :Black with White number From 3 cores: Black with White number + Green/Yellow

Sheath Colour :Transparent

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL OUTER SHEATH THICKNESS
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
2 0/75 0/4 0/8 7/2 79/3
2 1 0/4 0/8 7/6 91
2 1/5 0/4 0/8 8/2 110
2 2/5 0/5 0/8 9/4 147
3 0/75 0/4 0/8 7/5 91/3
3 1 0/4 0/8 7/9 104
3 1/5 0/4 0/8 8/6 129
3 2/5 0/5 0/9 10/1 185
3 4 0/6 1 12 269
3 6 0/65 1/1 13/5 354
3 10 0/75 1/3 16/9 579
3 16 0/75 1/5 19 785
3 25 0/9 1/8 23/5 1211
3 35 0/95 2 26/7 1642
4 0/75 0/4 0/8 8 107
4 1 0/4 0/8 8/5 124
4 1/5 0/4 0/8 9/2 151
4 2/5 0/5 0/9 11/1 230
4 4 0/6 1/1 13/2 332
4 6 0/65 1/2 14/8 442
4 10 0/75 1/5 18/8 735
4 16 0/75 1/6 20/9 988
4 25 0/9 2 26 1536
4 35 0/95 2/2 30 2098
4 50 1/25 2/6 35/3 2968
4 70 1/25 3 40/5 3822
4 95 1/6 3/6 49/4 5369
5 0/75 0/4 0/8 8/5 120
5 1 0/4 0/8 9/1 140
5 1/5 0/4 0/9 10/1 182
5 2/5 0/5 1 12/1 266
5 4 0/6 1/1 14/2 382
5 6 0/65 1/3 16/5 525
5 10 0/75 1/6 20/6 873
5 16 0/75 1/8 23/4 1207
5 25 0/9 2/2 29 1875
5 35 0/95 2/4 32/9 2577
 

ELECTRICAL CHARACTERISTICS

NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITES 30°C CONTINOUS LOADING
A
MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C
ohms/km
0/75 12 26
1 15 19/5
1/5 18 13/3
2/5 26 7/98
4 34 4/95
6 44 3/3
10 61 1/91
16 82 1/21
25 108 0/78
35 135 0/554
50 168 0/386
70 207 0/272
95 223 0/206