VDE 0295, VDE 0207-303-7, VDE 0293-308, VDE 0819-102, Flame Retardant according to IEC/EN 60332-1-2, IEC/EN 60332-3-24 Low Smoke Zero Halogen according to IEC/EN 60754-1/2, IEC/ EN 61034-1/2
APPLICATION
Veriflex halogen-free screened flexible connecting cables for use in mechanical engineering for instrumentation and control equipment and for tooling machinery production lines. Suitable for flexible applications for free movement without tensile load, in dry, moist and wet rooms. The screen protects against external interference pulses whilst the bedding provides additional mechanical protection. These cables are not used for outdoor or underground installation.
STANDARDS
CHARACTERISTICS
Voltage Rating Uo/U : 300/500V
Temperature Rating : Fixed: -40°C to +80°C Flexed: -15°C to +70°C
Minimum Bending Radius : Fixed: 6 x overall diameter Moved: 15 x overall diameter
CONSTRUCTION
Conductor : Class 5 flexible plain copper
Insulation :XLPE (Cross-linked Polyethylene)
Separator : PET (Polyester Tape)
Screen 1 : Al/PET (Aluminium Polyester Tape)
Screen 2 : TCWB (Tinned Copper Wire Braid)
Sheath :LSZH (Low Smoke Zero Halogen)
Core Identification : Black numbered + Green/Yellow
Sheath Colour :Black
DIMENSIONS
| NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm2 |
NOMINAL THICKNESS OF INSULATION mm |
NOMINAL THICKNESS OF OUTER SHEATH mm |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
|
| 2 | 0/5 | 0/4 | 0/8 | 6/8 | 77 | |
| 2 | 0/75 | 0/4 | 0/8 | 7/2 | 77 | |
| 2 | 1 | 0/4 | 0/9 | 7/8 | 107 | |
| 2 | 1/5 | 0/4 | 0/9 | 8/4 | 127 | |
| 3 | 0/5 | 0/4 | 0/8 | 7/1 | 89 | |
| 3 | 0/75 | 0/4 | 0/9 | 7/7 | 106 | |
| 3 | 1 | 0/4 | 0/9 | 8/1 | 120 | |
| 3 | 1/5 | 0/4 | 1 | 9 | 152 | |
| 3 | 2/5 | 0/5 | 1/1 | 11/1 | 243 | |
| 4 | 0/5 | 0/4 | 0/9 | 7/7 | 105 | |
| 4 | 0/75 | 0/4 | 0/9 | 8/2 | 123 | |
| 4 | 1 | 0/4 | 0/9 | 8/7 | 142 | |
| 4 | 1/5 | 0/4 | 1 | 9/6 | 178 | |
| 4 | 2/5 | 0/5 | 1/1 | 11/3 | 254 | |
| 4 | 4 | 0/6 | 1/3 | 13/6 | 371 | |
| 4 | 6 | 0/65 | 1/4 | 15/2 | 489 | |
| 4 | 10 | 0/75 | 1/7 | 19/2 | 766 | |
| 4 | 16 | 0/75 | 1/8 | 21/5 | 1062 | |
| 4 | 25 | 0/9 | 2/2 | 26/6 | 1577 | |
| 4 | 35 | 0/95 | 2/4 | 30/4 | 2096 | |
| 5 | 0/5 | 0/4 | 0/9 | 8/2 | 117 | |
| 5 | 0/75 | 0/4 | 0/9 | 8/7 | 138 | |
| 5 | 1 | 0/4 | 1 | 9/5 | 166 | |
| 5 | 1/5 | 0/4 | 1/1 | 10/5 | 208 | |
| 5 | 2/5 | 0/5 | 1/2 | 12/5 | 302 | |
| 5 | 4 | 0/6 | 1/3 | 14/9 | 463 | |
| 5 | 6 | 0/65 | 1/4 | 17/3 | 616 | |
| 5 | 10 | 0/75 | 1/8 | 21/2 | 946 | |
| 5 | 16 | 0/75 | 2 | 23/9 | 1315 | |
| 7 | 0/5 | 0/4 | 0/9 | 8/7 | 138 | |
| 7 | 0/75 | 0/4 | 1 | 9/5 | 167 | |
| 7 | 1 | 0/4 | 1 | 10/1 | 198 | |
| 7 | 1/5 | 0/4 | 1/1 | 11/2 | 251 | |
| 7 | 2/5 | 0/5 | 1/3 | 13/6 | 379 | |
| 7 | 4 | 0/6 | 1/4 | 16/2 | 588 | |
| 7 | 6 | 0/65 | 1/6 | 18/8 | 792 | |
| 12 | 0/5 | 0/4 | 1/1 | 11/1 | 213 | |
| 12 | 0/75 | 0/4 | 1/2 | 12/3 | 272 | |
| 12 | 1 | 0/4 | 1/2 | 13/1 | 316 | |
| 12 | 1/5 | 0/4 | 1/4 | 14/8 | 414 | |
| 18 | 0/75 | 0/4 | 1/3 | 14/1 | 367 | |
| 18 | 1 | 0/4 | 1/4 | 15/3 | 441 | |
| 18 | 1/5 | 0/4 | 1/5 | 17 | 569 | |
| 25 | 0/75 | 0/4 | 1/5 | 16/7 | 569 | |
| 25 | 1 | 0/4 | 1/6 | 18/3 | 611 | |
| 25 | 1/5 | 0/4 | 1/8 | 20/8 | 818 | |
ELECTRICAL CHARACTERISTICS
| NOMINAL CROSS SECTIONAL AREA mm2 |
CURRENT CARRYING CAPACITES 30°C CONTINOUS LOADING A |
MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C ohms/km |
||||
| 0/5 | 9 | 39 | ||||
| 0/75 | 12 | 26 | ||||
| 1 | 15 | 19/5 | ||||
| 1/5 | 18 | 13/3 | ||||
| 2/5 | 26 | 7/98 | ||||
| 4 | 34 | 4/95 | ||||
| 6 | 44 | 3/3 | ||||
| 10 | 61 | 1/91 | ||||
| 16 | 82 | 1/21 | ||||
| 25 | 108 | 0/78 | ||||
| 35 | 135 | 0/554 | ||||