H07RN-F AD8 EN 50525-2-21 Flexible Rubber Cable

APPLICATION

These cables are designed to provide high flexibility and have the capacity to withstand weather, oil/grease, mechanical and thermal stresses. Applications include handling equipment, mobile power supplies, worksites, stage and audio visual equipment, port areas and dams. Also for use in drainage and water treatment, cold environments and severe industrial environments. AD8 rated and suitable for installation in buried ducts

STANDARDS

EN 50525-2-21, EN 60228 Flame Retardant according to IEC/EN 60332-1-2 Water Resistant according to AD8

CHARACTERISTICS

Voltage Rating Uo/U : 450/750V Suitable for 1kV in fixed application

Temperature Rating : Fixed: -30°C to +90°C Flexed: - 15oC to +90oC

Minimum Bending Radius : Fixed: 4 x overall diameter Flexed: 6 x overall diameter

CONSTRUCTION

Conductor : Class 5 flexible copper conductor

Insulation :EPR (Ethylene Propylene Rubber)

Sheath :PCP (Polychloroprene)

Core Identification :1 core: Black 2 core: Blue Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/Yellow

Sheath Colour :Black

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm2
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
A2 GLANDS
Brass
A2PL GLAND
Plastic
1 1/5 0/8 5/8 52 20/16 20S
1 2/5 0/9 6/5 67 20/16 20S
1 4 1 7/4 92 20/16 20S
1 6 1 8/1 119 20S 20S
1 10 1/2 9/8 185 20S 20S
1 16 1/2 11/35 258 20 20
1 25 1/4 13/3 375 25 20
1 35 1/4 14/6 485 25 25
1 50 1/6 17/2 669 25 25
1 70 1/6 19/35 892 32 32
1 95 1/8 22/2 1160 32 32
1 120 1/8 24/3 1436 32 32
1 150 2 25/9 1748 40 40
1 185 2/2 29/7 2142 40 40
1 240 2/4 31/5 2698 50S 50S
1 300 2/6 36/5 3348 50 50S
1 400 2/8 40/4 4293 50 50
1 500 3 42/6 5262 50 50
1 630 3 47/2 6790 63S 63S
2 1 0/8 8/1 94 20S 20S
2 1/5 0/8 9 120 20S 20S
2 2/5 0/9 10/7 173 20S 20S
2 4 1 12/3 239 20 20
2 6 1 13/8 313 25 25
2 10 1/2 18/6 563 32 25
2 16 1/2 21/7 830 32 32
2 25 1/4 25/8 1211 40 40
3 1 0/8 8/74 117 20S 20S
3 1/5 0/8 9/68 147 20S 20S
3 2/5 0/9 11/48 123 20 20
3 4 1 13/2 297 25 25
3 6 1 14/78 390 25 25
3 10 1/2 19/9 705 32 32
3 16 1/2 23/31 1031 32 32
3 25 1/4 27/7 1512 40 40
3 35 1/4 30/2 1907 50S 50S
3 50 1/6 35/8 2651 50 50S
3 70 1/6 40/1 3484 50 50
3 95 1/8 46/4 4594 63S 63S
4 1 0/8 9/63 142 20S 20S
4 1/5 0/8 10/63 180 20S 20S
4 2/5 0/9 12/6 260 20 20
4 4 1 14/6 336 25 25
4 6 1 16/4 449 25 32
4 10 1/2 21/8 833 32 32
4 16 1/2 25/4 1138 40 40
4 25 1/4 30/7 1714 50S 50
4 35 1/4 33/4 2204 50S 50
4 50 1/6 39/6 3029 50 -
4 70 1/6 44/9 4121 63 -
4 95 1/8 51/9 5361 63 -
4 120 1/8 55/3 6546 - -
4 150 2 60/8 8095 - -
4 185 2/2 65/7 9652 - -
4 240 2/4 75/7 12614 - -
5 1/5 0/8 11/8 206 20 20L
5 2/5 0/9 14 297 25 25
5 4 1 16/2 422 25 25
5 6 1 18/2 567 32 32
5 10 1/2 24 1010 40 40
5 16 1/2 28/2 1400 40 40
5 25 1/4 33/9 2096 50S 50
5 35 1/4 37/2 2700 50 50
5 50 1/6 44 3730 63S 63S
5 70 1/6 48 5033 63 -
5 95 1/6 53/2 6271 63 -
7 1/5 0/8 15/13 315 25 25
7 2/5 0/9 17/6 445 25 32
12 1/5 0/8 18/2 493 25 32
12 2/5 0/9 21/4 702 32 32
19 1/5 0/8 22/1 710 32 32

CONDUCTORS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA
mm2
MAXIMUM DIAMETER OF WIRES IN CONDUCTOR
mm
MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/km
1 0/21 19/5
1.5 0/26 13/3
2.5 0/26 7/98
4 0/31 4/95
6 0/31 3/3
10 0/41 1/91
16 0/41 1/21
25 0/41 0/78
35 0/41 0/554
50 0/41 0/386
70 0/51 0/272
95 0/51 0/206
120 0/51 0/161
150 0/51 0/129
185 0/51 0/106
240 0/51 0/0801
300 0/51 0/0641
400 0/51 0/0486
500 0/61 0/0384
630 0/61 0/0287

ELECTRICAL CHARACTERISTICS (1mm2 to 2.5mm2)

Current Carrying Capacity and Mass Supportable

NOMINAL CROSS
SECTIONAL AREA
mm2
CURRENT CARRYING CAPACITY
Amps
MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CABLE
Single-Phase AC Three-Phase
 AC
1 10 10 5
1/5 16 16 5
2/5 25 20 5

Voltage Drop

NOMINAL CROSS
SECTIONAL AREA
mm2
DC OR SINGLE-PHASE AC
mV/A/m
THREE-PHASE AC
mV/A/m
1 46 40
1/5 32 27
2/5 19 16

Conductor operating temperature: 60ºC

ELECTRICAL CHARACTERISTICS (4mm2 and above)

Current Carrying Capacity
NOMINAL CROSS
SECTIONAL AREA
mm2
60°C CONDUCTOR OPERATING TEMPERATURE
Amps
85°C CONDUCTOR OPERATING TEMPERATURE**
Amps
Single-Phase AC Three-Phase AC Single-Phase AC Three-Phase AC
1 Two Core Cable, With or Without Protective Conductor 2 Single Core Cables 1 Three Core, Four Core or Five Core Cable 1 Two Core Cable, With or Without Protective Conductor 2 Single Core Cables Touching 1 Three Core, Four Core or Five Core Cable
4 30 - 26 41 - 36
6 39 - 34 53 - 47
10 51 - 47 73 - 64
16 73 - 63 99 - 86
25 97 - 83 131 - 114
35 - 140 102 - 192 140
50 - 175 124 - 240 170
70 - 216 158 - 297 216
95 - 258 192 - 354 262
120 - 302 222 - 414 303
150 - 347 255 - 476 348
185 - 394 291 - 540 397
240 - 471 343 - 645 467
300 - 541 394 - 741 537
400 - 644 - - 885 -
500 - 738 - - 1017 -
630 - 861 - - 1190 -
 

Ambient temperature: 30ºC Conductor operating temperature: 60ºC / 85ºC The above table for 60ºC conductor operating temperature is in accordance with Table 4F1A of the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52 ** 85ºC Table is in accordance with Table 4H2A of the 16th Edition of IEE Wiring Regulations. The current ratings tabulated are for cables in free air but may also be used for cables resting on a surface. If the cable is to be wound on a drum on load the ratings should be reduced in accordance with NOTE 2 below and for cables which may be covered, NOTE 3 below. 2. Flexible cables wound on reeling drums The current ratings of cables used on reeling drums are to be reduced by the following factors: a) Radial type drum b) Ventilated cylindrical type drum ventilated: 85% 1 layer of cable: 85% unventilated: 75% 2 layers of cable: 65% 3 layers of cable: 45% 4 layers of cable: 35% technicalspecification | 5 of 6 A radial type drum is one where spiral layers of cable are accommodated between closely spaced flanges; if fitted with solid flanges the ratings given above should be reduced and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated. A ventilated cylindrical cable drum is one where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable ventilating apertures. 3. Where cable may be covered or coiled up whilst on load, or the air movement over the cable restricted, the current rating should be reduced. It is not possible to specify the amount of reduction but the table of rating factors for reeling drums can be used as a guide.

DE-RATING FACTORS

FOR AMBIENT GROUND TEMPERATURES OTHER THAN 20ºC

AMBIENT TEMPERATURE 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC
DE-RATING FACTOR 1/07 1/04 1 0/96 0/93 0/89