(N)3GHSSHCH 12/20kV Cable

APPLICATION

کابل انعطاف پذیر برای تامین انرژی تجهیزات MV در کاربردهای تونل زنی و معدن کاوی زیرزمینی. نسخه پوششی هالوژن صفر دود کم (LSZH). مناسب برای کاربردهای داخلی و خارجی.

STANDARDS

VDE 0250 Part 605, VDE 0207, Flame Retardant according to IEC/EN 60332-1-2 Halogen Free according to IEC/EN 60754-1/2

CHARACTERISTICS

Voltage Rating Uo/U : 12/20kV      
Temperature Rating : 29kV           
Ambient Temperature Fixed: -40°C to +80°C
Flexed: +5°C to +80°C           
Minimum Bending Radiu Fixed: 6 x overall diameter
Flexed: 10 x overall diameter

CONSTRUCTION

Phase Conductor : Class 5 flexible stranded copper
Insulation : Rubber compound
Semi-Conductive Layers Semi-conductive tape over the conductor and inner and outer
semi-conductive rubber layer on the insulation
Protective Earth Conduc Individual copper wire screen
Control Conductor Class 5 flexible stranded tinned copper
Central Filler Rubber compound on a textile polyester support
First Inner Sheath LSZH (Low Smoke Zero Halogen)
Monitoring Conductor Copper wire screen, over the first inner sheath
Second Inner Sheath LSZH (Low Smoke Zero Halogen)
Armour Steel wire braid over the second inner sheath
Outr Sheath : LSZH (Low Smoke Zero Halogen)
Sheath Colour : Black      
 

DIMENSIONS

VOLTAGE
kV
NO. OF CORES (PHASE + EARTH
+ CONTROL+ÜL)
NOMINAL CROSS  SECTIONAL AREA
mm2
CONDUCTOR DIAMETER
mm
MINIMUM OVERALL DIAMETER
mm
MAXIMUM OVERALL DIAMETER
mm
MAXIMUM TENSILE LOAD
N
NOMINAL WEIGHT
kg/km
Phase Conductor Earth Conductor Control Conductor
12/20 3+3+3+ÜL 25 25/3E 2.5ST 6/1 52/9 58/2 1125 4330
12/20 3+3+3+ÜL 35 25/3E 2.5ST 7/2 54/7 60/2 1575 4780
12/20 3+3+3+ÜL 50 25/3E 2.5ST 8/9 58/3 64 2250 5540
12/20 3+3+3+ÜL 70 35/3E 2.5ST 10/6 61/7 67/8 3150 6570
12/20 3+3+3+ÜL 95 50/3E 2.5ST 12/3 65/2 71/5 4275 7690
12/20 3+3+3+ÜL 120 70/3E 2.5ST 13/8 68/7 75/3 5400 8920

CURRENT CARRYING CAPACITY

NOMINAL CROSS SECTIONAL AREA
mm2
LAYING ON THE FLOOR
Amps
REELED
Amps
1 Layer 2 Layer 3 Layer 4 Layer 5 Layer 6 Layer 7 Layer
25 139 111 85 68 58 53 38 31
35 172 138 105 84 72 65 46 38
50 216 173 132 106 91 82 58 48
70 265 212 162 130 111 101 72 58
95 319 255 195 156 134 121 86 70
120 371 297 226 182 156 141 100 82
150 428 342 261 210 180 163 116 94

Ambient temperature of 30°C

VOLTAGE DROP

NOMINAL CROSS
SECTIONAL AREA
mm2
POWER FACTOR
0/7 0/8 0/9 1
25 1/29 1/45 1/6 1/71
35 0/95 1/06 1/16 1/23
50 0/69 0/77 0/83 0/87
70 0/51 0/56 0/6 0/61
95 0/41 0/45 0/47 0/47
120 0/34 0/36 0/38 0/36
150 0/29 0/31 0/32 0/29

DE-RATING FACTORS

AMBIENT TEMPERATURE 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
DE-RATING FACTOR 1/08 1/04 1 0/96 0/91 0/87 0/82 0/76 0/71

اطلاعات ارائه شده در این برگه ، صرفاً جهت راهنمایی مهندسان طراح سیستمهای برق و کاربران است . تمامی اطلاعات با حسن نیت ارائه شده و اعتقاد بر این است که در زمان انتشار صحیح بوده است . هنگام انتخاب تجهیزات جانبی کابل لطفاً توجه داشته باشید که ابعاد واقعی کابل ممکن است به دلیل شرایط تولید متفاوت باشد .
کارشناسان این شرکت با افتخار ، آماده ارائه هرگونه اطلاعات فنی و مهندسی تکمیلی در خصوص این کابل و یا سایر کابلهای مورد نیاز پروژه شما میباشند .