Copper Conductor Single Core AWA LSZH BASEC 0.6/1kV Cable

APPLICATION

Single core LSZH cable with aluminium wire armour (AWA). Power and auxiliary fixed wiring cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.

STANDARDS

BS 6724, IEC/EN 60502-1, EN 60228, Low Smoke Zero Halogen according to IEC/EN 60754-1/2, IEC/EN 61034-2 Flame Retardant according to IEC/EN 60332-1-2, IEC/EN 60332-3-24 Cat C

CHARACTERISTICS

Voltage Rating Uo/U : 0.6/1kV

Temperature Rating : Fixed: -20°C to +90°C

Minimum Bending Radius : Fixed: 8 x overall diameter

CONSTRUCTION

Conductor : Class 2 stranded copper conductor

Insulation :XLPE (Cross-Linked Polyethylene)

Filler :PVC (Polyvinyl Chloride)

Armour :Double galvanized steel tape

Sheath :PVC (Polyvinyl Chloride)

Outer Sheath:PVC (Polyvinyl Chloride)

Core Identification :2 core: Blue Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/Yellow

Sheath Colour :Black

DIMENSIONS

NO. OF CORES NOMINAL CROSS SECTIONAL AREA
mm²
NOMINAL THICKNESS
OF INSULATION
mm
NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
BW / CW GLAND WRAPAROUND CLEATS
Under Armour Overall
1 50 1 12/7 17/5 800 20 CC7
1 70 1/1 14/7 20/2 960 25 CC8
1 95 1/1 16/6 22/3 1240 25 CC9
1 120 1/2 18/5 24/2 1510 25 CC10
1 150 1/4 20/8 27/4 1900 32 CC11
1 185 1/6 23/2 30 2320 32 CC12
1 240 1/7 26 32/8 2930 32 CC14
1 300 1/8 28/6 35/6 3580 40 CC16
1 400 2 32/4 40/5 4600 40 CC16
1 500 2/2 36 44/2 5770 50S CC18
1 630 2/4 40 48/8 7250 50 CC20
1 800 2/6 45/6 55/4 9381 63S -
1 1000 2/8 50/6 60/6 11540 63S -

CONDUCTORS

Class 2 Stranded Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS
SECTIONAL AREA
mm²
MINIMUM NO. OF WIRES IN CONDUCTOR MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
ohms/km
Circular Circular Compacted Shaped Annealed Copper Conductor
Cu Al Cu Al Cu Al Plain Wires
50 19 19 6 6 6 6 0/387
70 19 19 12 12 12 12 0/268
95 19 19 15 15 15 15 0/193
120 37 37 18 15 18 15 0/153
150 37 37 18 15 18 15 0/124
185 37 37 30 30 30 30 0/0991
240 37 37 34 30 34 30 0/0754
300 61 61 34 30 34 30 0/0601
400 61 61 53 53 53 53 0/047
630 91 91 53 53 53 53 0/0283
800 91 91 53 53 - - 0/0221
1000 91 91 53 53 - - 0/0176

ELECTRICAL CHARACTERISTICS XLPE/LSZH/AWA/LSZH

Current Carrying Capacity

NOMINAL CROSS
SECTIONAL AREA
mm²
REFERENCE METHOD C
(CLIPPED DIRECT)
Amps
REFERENCE METHOD F
(IN FREE AIR OR ON A PERFORATED CABLE TRAY, HORIZONTAL OR VERTICAL)
Amps
2 Cables Single- Phase AC or
DC Flat
3 or 4 Cables Three-Phase AC Flat 2 Cables Single-Phase AC or DC Flat 3 Cables Three-Phase AC Flat 3 Cables Three-Phase AC Trefoil 2 Cables DC 2 Cables
Single-Phase AC
3 or 4 Cables Three-Phase AC
Horizontal Vertical Horizontal Vertical Horizontal Vertical
50 237 220 253 232 222 284 270 282 266 288 266
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1137 1094 929 889 848 797
500 962 791 1016 851 918 1314 1266 1032 989 923 871
630 1082 861 1146 935 1027 1528 1474 1139 1092 992 940
800 1170 904 1246 987 1119 1809 1744 1204 1155 1042 978
1000 1261 961 1345 1055 1214 2100 2026 1289 1238 1110 1041

Ambient temperature: 30ºC

Conductor operating temperature: 90ºC

Notes

1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature

2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC , the current ratings given in the equivalent table for 70ºC thermoplastic insulated cables

VOLTAGE DROP

NOMINAL CROSS SECTIONAL AREA
mm²
TWO CORE CABLE DC REFERENCE METHOD C & F (CLIPPED DIRECT, ON TRAY OR IN FREE AIR)
mV/A/m
2 Cables Single-Phase AC 3 or 4 Cables Three-Phase AC
Touching Spaced* Trefoil and Touching Flat and Touching Flat and Spaced*
r x z r x z r x z r x z r x z
50 0/98 0/99 0/21 1 0/98 0/29 1 0/86 0/18 0/87 0/84 0/25 0/88 0/84 0/33 0/9
70 0/67 0/68 0/2 0/71 0/69 0/29 0/75 0/59 0/17 0/62 0/6 0/25 0/65 0/62 0/32 0/7
95 0/49 0/51 0/195 0/55 0/53 0/28 0/6 0/44 0/17 0/47 0/46 0/24 0/52 0/49 0/31 0/58
120 0/39 0/41 0/19 0/45 0/43 0/27 0/51 0/35 0/165 0/39 0/38 0/24 0/44 0/41 0/3 0/51
150 0/31 0/33 0/185 0/38 0/36 0/27 0/45 0/29 0/16 0/33 0/31 0/23 0/39 0/34 0/29 0/45
185 0/25 0/27 0/185 0/33 0/3 0/26 0/4 0/23 0/16 0/28 0/26 0/23 0/34 0/29 0/29 0/41
240 0/195 0/21 0/18 0/28 0/24 0/26 0/35 0/18 0/155 0/24 0/21 0/22 0/3 0/24 0/28 0/37
300 0/155 0/17 0/175 0/25 0/195 0/25 0/32 0/145 0/15 0/21 0/17 0/22 0/28 0/2 0/27 0/34
400 0/115 0/145 0/17 0/22 0/18 0/24 0/3 0/125 0/15 0/195 0/16 0/21 0/27 0/2 0/27 0/33
500 0/093 0/125 170 0/21 0/165 0/24 0/29 0/105 0/145 0/18 0/145 0/2 0/25 0/19 0/24 0/31
630 0/073 0/105 0/165 0/195 0/15 0/23 0/27 0/092 0/145 0/17 0/135 0/195 0/24 0/175 0/23 0/29
800 0/056 0/09 0/16 0/19 0/145 0/23 0/27 0/086 0/14 0/165 0/13 0/18 0/23 0/175 0/195 0/26
1000 0/045 0/092 0/155 0/18 0/14 0/21 0/25 0/08 0/135 0/155 0/125 0/17 0/21 0/165 0/18 0/24
Conductor operating temperature: 90ºC
r = Resistive Component
x = Reactive Component
z = Impedance Value
* Spacings larger than one cable diameter will result in a larger voltage drop.
For cables having conductors of 16mm2 or less cross sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having
conductors greater than 16mm2, cross sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive
component (mV/A/m)x

The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in goodfaith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.