NHXMH-J/O Cable

APPLICATION

این کابل ها برای نصب ثابت در اتاق های خشک و مرطوب و همچنین در ساختمان و بتن، داخل و زیر گچ در نظر گرفته شده اند؛ نه برای نصب زیرزمینی. برای تاسیساتی که در آن ها آتش سوزی، انتشار دود و گازهای سمی خطر بالقوه ای برای زندگی و تجهیزات ایجاد می کند.

STANDARDS

VDE 0250 part 214 Flame Retardant according to IEC/EN 60332-3-24

CHARACTERISTICS

Voltage Rating Uo/U : 300/500V

Temperature Rating : -5ºC to +70ºC

Minimum Bending Radius : 1.5mm2 to 10mm2: 4x overall diameter (red. to 2x OD at termination) 16mm2 and above: 5 x overall diameter (red. to 3x OD at termination

CONSTRUCTION

Conductor : 1.5mm2 to 10mm2: Class 1 solid Copper 16mm2 to 25mm2: Class 2 stranded Copper

Insulation :XLPE (Cross-Linked Polyethylene)

Filler :Halogen-free compound

Sheath :Halogen-free thermoplastic polymer compound

Core Identification :2 core: Blue Black 3 core: Yellow Red Black 4 core: Yellow Red Black Blue 5 core: Yellow Red Black Blue Green/Yellow

Sheath Colour :Gray

DIMENSIONS

NO. OF CORES NOMINAL CROSS
 SECTIONAL AREA
mm2
CONDUCTOR CLASS NOMINAL OVERALL DIAMETER
mm
NOMINAL WEIGHT
kg/km
1 1/5 1 5/2 92
1 2/5 1 5/6 110
1 4 1 7/1 135
1 6 1 7/4 160
1 10 1 7/8 215
1 16 2 8/8 295
2 1/5 1 8/2 110
2 2/5 1 9 130
2 4 1 9/8 173
3 1/5 1 8/7 120
3 2/5 1 9/6 159
3 4 1 11 223
3 6 1 12/5 320
3 10 1 15 520
3 16 2 19/7 850
4 1/5 1 9/2 151
4 2/5 1 10/2 200
4 4 1 12/2 300
4 6 1 13/2 395
4 10 1 15/8 595
4 16 2 20 935
5 1/5 1 10 168
5 2/5 1 11/1 238
5 4 1 13/6 350
5 6 1 15 480
5 10 1 17/7 773
5 16 2 22 1290
5 25 2 27 1725

CONDUCTORS

Class 1 Solid Conductors for Single Core and Multi-Core Cables

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC ohms/km NOMINAL CROSS SECTIONAL AREA mm2
Circular, Annealed Copper Conductor
Plain Wires
12/1 1/5
7/41 2/5
4/61 4
3/08 6
1/83 10

Class 2 Stranded Conductors for Single Core and Multi-Core Cables

NOMINAL CROSS SECTIONAL AREA
mm2
MINIMUM NO. OF WIRES IN CONDUCTOR MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
Circular Annealed Copper Conductor
CU Plain wires
ohms/km
16 7 7 - - 1/15
25 7 7 6 6 0/727

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity

Conductor
cross- sectional
area
Reference Method A
(enclosed in conduit in
thermally insulating wall etc.)
Reference Method B
(enclosed in conduit on a wall or
in trunking etc.)
Reference Method C
(clipped direct)
1 two-core
cable,
single-phase
AC or DC
1 three- or
four-core cable
three-phase
AC
1 two-core
cable,
single-phase
AC or DC
1 three- or
four-core cable
three-phase
AC
1 two-core
cable,
single-phase
AC or DC
1 three- or
four-core cable
three-phase
AC
1 2 3 4 5 6 7
(mm2) (A) (A) (A) (A) (A) (A)
1/5 18/5 16/5 22 19/5 24 22
2/5 25 22 30 26 33 30
4 33 30 40 35 45 40
6 42 38 51 44 58 52
10 57 51 69 60 80 71
16 76 68 91 80 107 96
25 99 89 119 105 138 119

Multicore 90°C thermosetting insulated and thermoplastic sheathed cables, non-armoured (COPPER CONDUCTORS)

Ambient temperature: 30°C Conductor operating temperature:90°C

VOLTAGE DROP (per ampere per metre)

Conductor
cross- sectional area
Two-core cable
DC
Two-core cable, single-phase
AC
Three- or four-core cable, three-phase
AC
  2 3 4
(mm2) (mV/A/m) (mV/A/m) (mV/A/m)
1 46 46 40
1/5 31 31 27
2/5 19 19 16
4 12 12 10
6 7/9 7/9 6/8
10 4/7 4/7 4
16 2/9 2/9 2/5

Conductor operating temperature: 90°C